How to use the egress width calculator
Forty-four inches is the floor. Capacity can ask for more.
The egress width calculator answers one question: for this occupant load, how wide does this stair, door, or corridor have to be? It compares the capacity width with the dimensional minimum and tells you which one governs. The tool is at /calculators/egress-width. The reasoning is the means of egress guide and the corridor and door width guide. Both describe the 2021 IBC method in Section 1005: the larger of capacity and the minimum. The chapter is at ICC.
The tool's bundled 2021 factors match that guide. Stairs use 0.3 inch per occupant, and other egress components use 0.2 inch per occupant. The reduction, to 0.2 and 0.15, applies only when the building is sprinklered under Section 903.3.1.1 or 903.3.1.2 and has an emergency voice/alarm system under Section 907.5.2.2. The checkbox is labeled for that combination. Do not check it because the building has sprinklers and a horn. A horn is not an emergency voice/alarm communication system. If you are not sure, leave the box off and design to the larger factor. Confirm the subsection numbers in the adopted code. Cities amend this reduction.
How to run it.
Get the occupant load from the occupant load calculator first. The width tool can import that number. A guessed load makes a precise width that is still wrong.
Run the component you are sizing. A door and a corridor do not share a minimum. The tool knows a 32-inch clear door and a 44-inch corridor, and a 36-inch corridor where the load is under 50. Those minimums are dimensional. Capacity can exceed them. A corridor that "meets 44 inches" can still fail. That is the whole point of the width guide.
Run stairs separately from doors. Then look at swing and hardware, which this calculator does not do. Fifty or more occupants changes the swing. That is the panic hardware guide.
The mistake is checking the sprinkler box on a 13R building, or on a building with no voice alarm, and issuing the narrower stair. Write the assumption on the code sheet next to the width: sprinkler standard, and whether the voice/alarm system exists.
Confirm the edition on the jurisdictions page. Then upload the life-safety plan and run a free scan. The calculator is the math. The plan is what the reviewer measures.
This is advisory. It is not a determination by the authority having jurisdiction. Confirm the adopted edition and local amendments before you change a drawing.