Does a two-story building need an elevator? IBC 1104.4 vs. ADA 206.2.3

The ADA and the IBC both exempt some upper floors from an accessible route. They use different tests, and a building can pass one and fail the other.

InstaPreView · Published November 17, 2026 · Updated November 17, 2026
Line drawing of a two-story building section with an elevator shaft and a stair, titled “Does a two-story building need an elevator? IBC 1104.4 vs. ADA 206.2.3”. InstaPreView by Byts & Bytes.

A designer sets up a two-story office: 9,000 square feet on the ground floor, 6,000 on the second, stairs only. The owner's consultant says the ADA does not require an elevator in a building under three stories. The plan reviewer comments anyway: "Provide an accessible route to the second floor. IBC 1104.4."

Both of them read their code correctly. The ADA Standards and the IBC each have an exception for stories above and below the accessible level, and the two exceptions use different tests. A building can pass one and fail the other.

The IBC rule

2021 IBC Section 1104.4 says at least one accessible route shall connect each accessible story, mezzanine and occupied roof in multilevel buildings and facilities. Section 1104.3 points back to it: stories and mezzanines exempted by 1104.4 do not need the accessible route that would otherwise serve every portion of the building.

The 2021 IBC has four exceptions.

Exception 1, the 3,000 square foot test. An accessible route is not required to stories, mezzanines and occupied roofs that have an aggregate area of not more than 3,000 square feet and are located above and below accessible levels. The exception does not apply to:

  • Group M multiple-tenant facilities with five or more tenant spaces used for the sales or rental of goods, where at least one of those tenant spaces is above or below the accessible levels.
  • Stories or mezzanines containing offices of health care providers (Group B or I).
  • Passenger transportation facilities and airports (Group A-3 or B).
  • Government buildings.
  • Structures with four or more dwelling units.

The word that matters is aggregate. The 3,000 square feet is the total of every non-accessible story, mezzanine and occupied roof together, not a per-floor limit.

Exception 2. Stories, mezzanines or occupied roofs that do not contain accessible elements or other spaces as determined by Section 1108 or 1109 do not need an accessible route from an accessible level.

Exception 3. In air traffic control towers, the cab and the floor immediately below it.

Exception 4. In a two-story building, a story or mezzanine with an occupant load of five or fewer persons that does not contain public use space does not need to be connected to the story above or below.

The ADA rule

The 2010 ADA Standards, Section 206.2.3 also requires at least one accessible route to connect each story and mezzanine. Its first exception reads differently. In private buildings or facilities that are less than three stories or that have less than 3,000 square feet per story, an accessible route is not required to connect stories, as long as the building is not a shopping center, a shopping mall, the professional office of a health care provider, a public transportation terminal, depot or station, an airport passenger terminal, or another type of facility the Attorney General determines.

Two differences from the IBC stand out:

  • The ADA test is "or." A private building under three stories qualifies no matter how big the floors are.
  • The ADA measures 3,000 square feet per story. The IBC measures the aggregate of the floors above and below the accessible level.

The ADA's other exceptions include a two-story public building with one story of five or fewer occupants and no public use space (close to IBC Exception 4), plus rules for detention facilities, residential facilities, transient lodging, air traffic control towers, and qualified historic buildings.

Running the example

Go back to the 6,000 square foot second floor. Under ADA 206.2.3 Exception 1, a private two-story office is under three stories, so the ADA does not require the elevator. Under IBC 1104.4 Exception 1, the second floor is 6,000 square feet, which is over the 3,000 aggregate limit, so the exception does not apply. The building code still needs the accessible route.

Shrink the second floor to 2,400 square feet and the IBC exception can work, unless one of the five carve-outs applies. Lease that floor to a dentist and it fails again: a story containing offices of a health care provider is excluded under both documents.

A local permit is reviewed against the adopted building code. Meeting the ADA exception does not answer the IBC comment, and the reverse is also true. The ADA is a federal law that applies on its own terms, separate from the local building code.

What the exemption does not cover

  • The rest of the floor still has to comply. The ADA advisory to 206.2.3 says spaces and elements located on a level not required to be served by an accessible route must fully comply with the Standards. Toilet rooms, door hardware and counters on an exempt second floor are not off the hook.
  • Dining areas. 2021 IBC 1109.2.9 requires dining and drinking areas to be accessible and on an accessible route. Its first exception allows stories above or below only where 1104.4 Exception 1 permits it.
  • Mezzanines are not stories. The ADA advisory notes that a mezzanine may be a change in level, but it is not a story. If an accessible route is required to connect stories, it has to serve the mezzanines too. The mezzanines guide covers how the IBC defines one.

What to put on the code sheet

When a stair-only multistory scheme relies on an exception, say so on the code analysis sheet:

  • Which section and exception you are using (for example, "2021 IBC 1104.4, Exception 1").
  • The area of each story above and below the accessible level, and their aggregate.
  • The tenant type on each non-accessible floor, so the reviewer can see none of the carve-outs apply.
  • The adopted edition. Confirm it on the code adoption tracker or your jurisdiction page, and read any local amendment to Chapter 11.

The accessible routes guide and the IBC vs. ADA vs. A117.1 guide go deeper on how the documents fit together. The occupant load calculator helps check Exception 4's five-person limit.

Run a free scan on the set. A second floor shown as "storage" on the code sheet and "offices" on the floor plan is the kind of mismatch the scan can surface before the reviewer does.

This is advisory. It is not a determination by the authority having jurisdiction. Confirm the adopted edition and local amendments before you change a drawing.