These notes came from the code corpus for Raleigh, NC. They are not a published rejection ranking from the building department, and they are not human-verified. Corpus trust label: provisional.
energy · high · 2018 NC Energy Conservation Code (based on ASHRAE 90.1-2016 or IECC 2018)
COMcheck or energy compliance documentation has not been submitted or does not demonstrate compliance with the 2018 NC Energy Conservation Code.
Submit a completed COMcheck Envelope, Mechanical, and Lighting compliance report (or equivalent) showing compliance; ensure insulation, fenestration, and system efficiencies meet Climate Zone 3 (Raleigh/Wake County) requirements.
fire · high · 2018 NCBC 705 / IBC 705 (Exterior Walls – Fire Separation Distance)
Exterior wall fire-resistance rating and/or opening protection does not comply with the required fire separation distance from the property line or adjacent building.
Provide fire-rated exterior wall construction and limit/protect openings per Table 705.8 based on the actual fire separation distance and occupancy.
completeness · medium · 2018 NCBC 1209 / IBC 1209 & Wake County / Raleigh Zoning
Toilet room location, privacy, or accessibility compliance has not been demonstrated; accessible toilet room features (turning radius, grab bars, fixture heights) are missing from drawings.
Provide dimensioned restroom plans showing 60-inch turning radius, grab bar locations and heights, accessible fixture clearances, and accessible route to restroom per ICC A117.1-2009 and NC Building Code Chapter 11.
occupancy · high · IBC 1004.1 (NC State Building Code, based on 2018 IBC)
Proposed occupancy classification or occupant load is incorrect or not justified for the intended use.
Recalculate occupant load based on IBC Table 1004.5 or provide justification for proposed classification/load. Ensure it aligns with egress and plumbing requirements.
accessibility · high · IBC 1104.2 (NC State Building Code, Chapter 11)
An accessible route is not provided to all required areas (e.g., building entrance, primary function areas, accessible restrooms, employee workstations).
Design an accessible route free of level changes, excessive slopes (max 1:12 for ramps), or obstructions, providing minimum 36-inch clear width to all required spaces.
structural · high · IBC 1607.1, Table 1607.1 (NC State Building Code, based on 2018 IBC)
Floor live loads shown are less than required for the proposed occupancy or use, or are not clearly specified.
Specify minimum required live loads per IBC Table 1607.1 for all areas and verify structural capacity. If actual loads exceed code minimums, design for actual loads.
accessibility, plumbing · high · IBC 1109.2 (NC State Building Code, Chapter 11), IPC 403.1
Restrooms do not meet accessible design requirements (e.g., clear floor space, grab bars, turning radius, fixture clearances).
Redesign restrooms to comply with all accessible restroom requirements, including specific dimensions for fixture clearances, grab bars, turning space (60-inch diameter), and accessible accessories.
energy · medium · IECC C402.2 (NC Energy Code, based on 2018 IECC)
Proposed building envelope components (walls, roof, fenestration) do not meet prescriptive U-factor, C-factor, or SHGC requirements for Climate Zone 3.
Specify insulation R-values, window U-factors, and SHGC values that meet or exceed prescriptive requirements, or provide whole-building performance method compliance (e.g., COMcheck report).
mechanical · high · IMC 403.2, Table 403.3.1.1 (NC Mechanical Code, based on 2018 IMC)
Proposed ventilation rates (outdoor air supply) are insufficient for the occupant load and space type.
Increase outdoor air supply rates to meet minimum requirements based on occupant load and area per IMC Table 403.3.1.1. Provide detailed ventilation calculations.
fire · high · IBC 707, 708, 709, 710, 508.4 (NC State Building Code, based on 2018 IBC)
Fire rating of proposed walls, floor/ceiling assemblies, or opening protectives is less than required for the separation type or occupancy.
Increase the fire resistance rating of the assembly to meet required hours per IBC tables (e.g., 1-hour for business separation, 2-hour for exit enclosures). Ensure firestopping and opening protectives are compliant.
completeness · high · IBC 107.2, 107.3 (NC State Building Code, based on 2018 IBC)
Construction documents are incomplete or lack sufficient detail for review (e.g., missing scope of work, structural calculations, energy compliance forms, specific details, or professional seals).
Provide all required construction documents, including detailed plans, elevations, sections, schedules, specifications, calculations, energy compliance forms (e.g., COMcheck), and proper professional seals and signatures.
plumbing · medium · IPC 403.1, Table 403.1 (NC Plumbing Code, based on 2018 IPC)
Number of plumbing fixtures (water closets, lavatories, drinking fountains) is insufficient for the calculated occupant load.
Add additional plumbing fixtures to meet the minimum requirements based on occupant load and gender split per IPC Table 403.1.
egress · high · IBC 1006.2.1 (NC State Building Code, based on 2018 IBC)
Number of exits provided is less than required for the calculated occupant load or area.
Add additional exits to meet the minimum count based on occupant load and building characteristics (e.g., 2 exits for 31-500 occupants, 3 for 501-1000).
occupancy · medium · 2018 NC Mechanical Code 401 / IMC 401 (Ventilation)
Outdoor air ventilation rates are not shown or do not meet minimum requirements for the occupancy type and occupant density.
Provide HVAC schedules and calculations demonstrating minimum outdoor air per Table 403.3.1.1 of the NC Mechanical Code (or ASHRAE 62.1 path); note ventilation rates on mechanical drawings.
accessibility · high · 2018 NC Building Code Chapter 11 / ICC A117.1-2009
Accessible route from public way to the primary entrance and throughout the tenant space is not clearly shown or does not comply with dimensional requirements.
Provide a complete accessible route plan; verify door clear widths (32 in min), maneuvering clearances, ramp slopes (1:20 max without handrails, 1:12 max ramp), and signage.
egress · high · IBC 1006.2 / 2018 NC Building Code 1006.2
Insufficient number of exits or exit access doorways provided for the occupant load or travel distance shown.
Provide the minimum number of exits per Table 1006.2.1; ensure no single exit serves more than the permitted occupant load.
fire · high · IBC 403 / 2018 NC Fire Code & NFPA 13
Automatic fire sprinkler system required but not shown on the submitted drawings.
Provide NFPA 13 or 13R sprinkler system drawings signed and sealed by a licensed fire protection engineer or contractor; coordinate with Raleigh Fire Department permit.
plumbing · high · 2018 NC Plumbing Code Table 403.1 (based on IPC Table 403.1)
Insufficient number of plumbing fixtures provided for the calculated occupant load and occupancy type.
Recalculate fixture counts per NC Plumbing Code Table 403.1 for the specific occupancy; add water closets, lavatories, and drinking fountains as required.
completeness · high · 2018 NCBC 107.2 / Raleigh Development Services Submittal Requirements
Drawings are incomplete: missing one or more required elements such as a code analysis sheet, occupant load calculations, life safety plan, or engineer/architect seal.
Provide a code analysis sheet noting occupancy classification, construction type, sprinkler status, occupant loads, and egress summary. Ensure all sheets are signed and sealed by NC-licensed design professionals as required.