These notes came from the code corpus for Reno, NV. They are not a published rejection ranking from the building department, and they are not human-verified. Corpus trust label: provisional.
accessibility · high · IBC 1104.2, ICC A117.1 403
A continuous accessible route is not provided to all required spaces, or the clear width of accessible routes (e.g., corridors, doorways) is insufficient.
Provide a continuous accessible route to all required functional spaces. Ensure minimum clear width of 36 inches (except at doors) and proper maneuvering clearances are maintained.
egress · high · IBC 2021 § 1005.1
Corridor/exit access width is insufficient for the calculated occupant load. Minimum 44 inches required where occupant load ≥ 50.
Widen corridor to at least 44 inches clear, or redesign egress path to meet minimum width per occupant load calculation.
egress · high · IBC 1017.2
The exit access travel distance from any point in the building to the nearest exit exceeds the maximum allowed by IBC Table 1017.2.
Reconfigure the floor plan to reduce travel distances to an approved exit, or add additional exits to comply with the maximum travel distance limits.
fire · high · IBC 907.2
A fire alarm system is required throughout the building or in specific areas but is not indicated or designed.
Provide an approved fire alarm system conforming to NFPA 72 as required by IBC 907.2 for the building's specific characteristics.
egress · high · IBC 1008.2, 1013.1, 1013.6
Emergency egress illumination is not provided along all means of egress paths, or exit signs are missing, not illuminated, or not located in accordance with code requirements.
Provide approved emergency lighting to maintain minimum illumination levels in all egress paths. Install and illuminate exit signs at all required exit doors and where the egress path is not apparent.
fire · high · IBC 903.2
An automatic sprinkler system is required throughout the building or in specific areas but is not indicated or designed.
Provide an approved automatic sprinkler system conforming to NFPA 13, 13R, or 13D as required by IBC 903.2 for the building's specific characteristics.
fire · high · IBC 703.1, 706.1
Fire-resistance rated assemblies are not clearly identified or detailed, or penetrations through such assemblies are not properly protected with approved firestopping.
Clearly identify all fire-resistance rated assemblies on the plans, including required ratings and construction methods. Provide details for all firestopping, fire dampers, and opening protectives at penetrations and openings.
accessibility · high · IBC 1109.2, ICC A117.1 603
Toilet room accessibility requirements, including clear floor space, grab bar locations, fixture heights, and maneuvering clearances, are not met.
Ensure all required accessible toilet rooms comply with the specific dimensional and fixture requirements of ICC A117.1 Chapter 6.
occupancy · high · IBC 302.1, 508.4
Proposed occupancy classification is not correctly identified, or required fire-resistance rated separations between mixed occupancies are inadequate or missing.
Correct occupancy classification based on IBC Chapter 3. Provide all required fire-resistance rated separations, area limitations, and sprinkler provisions per IBC Chapter 5.
plumbing · medium · IPC 403.1, Table 403.1
The number of plumbing fixtures (water closets, lavatories, drinking fountains) provided does not meet the minimum requirements for the proposed occupant load and occupancy classification.
Provide the required number of plumbing fixtures based on IPC Table 403.1 for the calculated occupant load and proposed occupancy.
energy · medium · IECC C402, C403, C405
Building envelope components (e.g., insulation, fenestration), HVAC systems, or lighting designs do not demonstrate compliance with IECC requirements.
Provide energy compliance documentation (e.g., COMcheck report) detailing U-factors, R-values, SHGC, mechanical equipment efficiencies, and lighting power densities that meet 2018 IECC standards.
egress · high · IBC 1004.1, 1006.2
Occupant load calculation is incorrect, leading to an insufficient number of required exits or inadequate egress capacity.
Recalculate occupant load for all areas based on IBC Table 1004.5. Ensure the minimum number of exits and total egress width are provided.
mechanical · medium · IMC 403.3, Table 403.3.1.1
Mechanical ventilation rates for outdoor air supply or exhaust are not adequate for the proposed occupancy or space type.
Ensure mechanical ventilation systems are designed to deliver outdoor air at rates specified in IMC Table 403.3.1.1 for each space, based on occupant load and floor area.
structural · high · IBC 1603.1.1, 1603.1.2, 1603.1.5
Local design criteria for ground snow load, wind speed, or seismic design category are not correctly specified on the plans.
Indicate the correct design criteria on the plans as required by the City of Reno: Ground Snow Load = 30 psf, Wind Speed = 115 mph (3-sec gust), Seismic Design Category D (for Site Class C as per ASCE 7-16 and local site conditions).