fire · high · NFPA 13 / IBC 2021 § 903.3.1.1
Automatic fire sprinkler system is required but not shown on plans, or the system is not designed to NFPA 13 standards.
Provide hydraulically designed automatic sprinkler system per NFPA 13; include hydraulic calculations, head spacing, and water supply data.
egress · medium · IBC 1010.1.3 / 1105.1
Egress or accessible doors are shown to open against the direction of egress travel (where prohibited), or do not have adequate clear width, or are missing required hardware (e.g., panic hardware).
Ensure doors serving spaces with an occupant load of 50 or more open in the direction of egress travel. Verify all accessible doors meet minimum clear width and opening force requirements. Specify compliant door hardware (e.g., panic hardware where required).
accessibility · high · IBC 1104.2 (ADA/ANSI A117.1)
An accessible route is not clearly shown or does not meet minimum dimensions (e.g., width, slope, head height) from the site arrival point to all accessible spaces and elements within the building.
Provide a continuous, compliant accessible route that meets ADA Standards and ANSI A117.1 requirements, connecting all accessible building entrances, public spaces, and elements.
egress · high · IBC 1028.1 / 1029.1
The means of egress does not lead directly to a public way or an approved safe area of refuge; or the exit discharge is obstructed, inadequate, or does not meet minimum dimensions.
Ensure all exits discharge directly or via an approved exit discharge system to a public way or a safe dispersal area. Remove all obstructions from the exit discharge path.
egress · high · IBC 2021 § 1005.1 / Houston Amendment
Egress corridor width is less than the minimum required 44 inches for an occupant load exceeding 50.
Widen corridor to a minimum of 44 inches clear of all obstructions, projections, and handrails.
accessibility · high · 2010 ADA Standards / TAS (Texas Accessibility Standards) § 4.1 / Texas Gov't Code Ch. 469
Plans do not demonstrate compliance with Texas Accessibility Standards (TAS). TDLR registration and RAS (Registered Accessibility Specialist) review are required.
Register project with TDLR, retain a Registered Accessibility Specialist, and revise plans to meet TAS requirements including accessible routes, restrooms, parking, and signage.
energy · medium · 2021 IECC (Commercial) / Texas Local Amendments – Texas Energy Code
Energy compliance documentation (COMcheck or equivalent) is not included in the submittal or does not demonstrate compliance with the Texas Energy Code.
Submit a completed COMcheck report (or equivalent energy compliance report) for envelope, lighting, and mechanical systems demonstrating compliance with the adopted Texas Energy Code.
accessibility · high · TAS § 4.6 / 2010 ADA § 208
Insufficient number of accessible parking spaces provided, or van-accessible spaces not correctly located or dimensioned.
Provide accessible spaces per TAS Table 208.2 (e.g., 1 of every 6 accessible spaces must be van-accessible, 132-inch-wide access aisle for van spaces).
completeness · medium · Houston Code of Ordinances Ch. 10 / Houston Building Code – Submittal Requirements
Submittal is incomplete: missing required documents such as site plan, construction type statement, occupancy classification, design professional seal, or geotechnical report (if required).
Provide all documents required by the City of Houston permit submittal checklist including signed/sealed drawings by a Texas-licensed architect or engineer, site plan with setbacks, and applicable reports.
egress · high · IBC 1008.2 / 1008.3 / 1013.1
Emergency lighting or exit signs are missing, incorrectly located along egress paths, or do not meet illumination requirements for continuous operation during power outages.
Provide emergency lighting systems capable of illuminating egress paths to 1 footcandle average for 90 minutes. Install and properly illuminate exit signs along all required exit routes, connected to an emergency power source.
fire · high · IBC 907.2
A fire alarm system is required for the occupancy/building type (e.g., Group A with >300 occupants, Group E) but is not indicated or designed according to NFPA 72 standards.
Provide a design for a code-compliant fire alarm system, including initiation devices, notification appliances, and control functions as required by IBC 907.2 and NFPA 72.
completeness · high · IBC 107.2
Construction documents are incomplete or lack sufficient detail to demonstrate code compliance (e.g., missing scope of work, material specifications, egress paths, fire ratings, or structural details).
Revise and resubmit construction documents to include all required information as per IBC Chapter 1, ensuring clarity and completeness for plan review.