Clear floor space and knee and toe clearance: ADA 305 and 306

The 30-by-48-inch clear floor space in Section 305, alcove widths, and the knee and toe clearance envelope in Section 306 that decides what space under a fixture you can count.

InstaPreView · Published November 20, 2026 · Updated November 20, 2026
Line drawing of a tenant floor plan with demising walls and one suite outlined, titled “Clear floor space and knee and toe clearance: ADA 305 and 306”. InstaPreView by Byts & Bytes.

A wall-hung lavatory is drawn with a 30-by-48-inch clear floor space centered on the bowl, half of it under the fixture. The accessibility reviewer writes: "Knee clearance under the lavatory is 8 inches deep at 9 inches above the floor. 306.3.3 requires 11 inches." The plan showed the clear floor space. It did not show the knee and toe envelope that space is allowed to use.

The 30-by-48-inch clear floor space

The 2010 ADA Standards for Accessible Design, also published by the U.S. Access Board, put the basic clear floor or ground space in Section 305:

  • 305.3 Size. "The clear floor or ground space shall be 30 inches (760 mm) minimum by 48 inches (1220 mm) minimum."
  • 305.2 Floor or ground surfaces. Those surfaces shall comply with 302, and changes in level are not permitted.
  • 305.5 Position. Unless otherwise specified, the space shall be positioned for either a forward or a parallel approach to the element.
  • 305.6 Approach. "One full unobstructed side of the clear floor or ground space shall adjoin an accessible route or adjoin another clear floor or ground space."
  • 305.4 Knee and toe clearance. Unless otherwise specified, the clear floor or ground space may include knee and toe clearance complying with 306.

Section 309.2 requires that same 305 space at operable parts. Section 603.2.2 and Section 604.3.2 allow it to overlap turning space and the water closet clearance. The accessible water closet calculator and the ADA reach range calculator both depend on this rectangle. This guide is the place to check the rectangle itself, and the space under a fixture that it is allowed to use.

Alcoves

Section 305.7 adds maneuvering clearance when the clear floor space is in an alcove, or is otherwise confined on all or part of three sides:

  • 305.7.1 Forward approach. "Alcoves shall be 36 inches (915 mm) wide minimum where the depth exceeds 24 inches (610 mm)."
  • 305.7.2 Parallel approach. "Alcoves shall be 60 inches (1525 mm) wide minimum where the depth exceeds 15 inches (380 mm)."

A 30-inch-wide alcove is not enough once the recess is deeper than those limits. The extra width is for maneuvering into the space, not a substitute for the 30-by-48-inch space itself.

When space under a fixture counts

Section 306.1:

"Where space beneath an element is included as part of clear floor or ground space or turning space, the space shall comply with 306. Additional space shall not be prohibited beneath an element but shall not be considered as part of the clear floor or ground space or turning space."

You may have leftover room under a counter. Only the portion that meets 306 can be counted toward the 30-by-48-inch space or the turning space. The Access Board advisory to 306.1 adds that clearances are measured in relation to the usable clear floor space, not necessarily to the vertical support for an element, and that the space should be checked for obstructions.

Turning space in Section 304.3 may also include knee and toe clearance complying with 306. This guide does not restate the 60-inch circular or T-shaped turning space rules; it covers the under-fixture envelope those spaces are allowed to use.

Toe clearance

Toe clearance is the space under an element from the finish floor up to 9 inches (Section 306.2.1). The rules in 306.2 are:

  • 306.2.2 Maximum depth. Toe clearance shall extend 25 inches (635 mm) maximum under an element.
  • 306.2.3 Minimum required depth. Where toe clearance is required at an element as part of a clear floor space, it shall extend 17 inches (430 mm) minimum under the element.
  • 306.2.4 Additional clearance. Space extending more than 6 inches (150 mm) beyond the available knee clearance at 9 inches above the floor shall not be considered toe clearance.
  • 306.2.5 Width. Toe clearance shall be 30 inches (760 mm) wide minimum.

The 6-inch limit in 306.2.4 is easy to miss. Toes cannot be counted in a deep pocket that sticks out more than 6 inches past the knee clearance immediately above them.

Knee clearance

Knee clearance is the space under an element between 9 inches and 27 inches above the finish floor (Section 306.3.1). The rules in 306.3 are:

  • 306.3.2 Maximum depth. Knee clearance shall extend 25 inches (635 mm) maximum under an element at 9 inches above the finish floor or ground.
  • 306.3.3 Minimum required depth. Where knee clearance is required under an element as part of a clear floor space, it shall be 11 inches (280 mm) deep minimum at 9 inches above the finish floor or ground, and 8 inches (205 mm) deep minimum at 27 inches above the finish floor or ground.
  • 306.3.4 Clearance reduction. Between 9 and 27 inches above the floor, the knee clearance may reduce at a rate of 1 inch in depth for each 6 inches in height.
  • 306.3.5 Width. Knee clearance shall be 30 inches (760 mm) wide minimum.

The 11-inch depth at 9 inches above the floor, tapering to 8 inches at 27 inches, is the envelope a forward approach under a lavatory or counter has to meet. A pipe, a cabinet bottom, or a sharp reduction that cuts inside that slope is a typical comment. The 1-in-6 reduction in 306.3.4 is a permission, not a requirement to slope the underside.

A forward reach over an obstruction in Section 308.2.2 also requires the clear floor space to extend under the element for a distance not less than the reach depth. That under-element space still has to be real knee and toe clearance under 306. See ADA reach ranges: forward vs. side.

How this shows up in a restroom

At a lavatory, the 30-by-48-inch clear floor space is usually a forward approach, with part of the 48-inch depth under the bowl. The exposed under-fixture volume has to meet 306, including the 11-inch knee depth at 9 inches above the floor. That same clear floor space may overlap the water closet clearance under 604.3.2, which is covered in Water closet clearance: ADA 604.3. A door may not swing into this clear floor space, with the two exceptions in 603.2.3, covered in Restroom door swing: ADA 603.2.3.

What the 2010 ADA Standards do not settle here

Buildings permitted under the International Building Code also have to meet the ICC A117.1 edition that the adopted IBC references. This post does not quote A117.1. Confirm the standard and edition the authority having jurisdiction enforces, and see IBC, ADA, and ICC A117.1: which accessibility rule applies.

Check the space

The ADA reach range calculator applies the 308 height limits and notes, without calculating, the 306 clearance under a forward-reach obstruction. The accessible water closet calculator checks the water closet clearance and the lavatory only to the extent the 604 rules require. Neither one replaces a dimensioned 305 rectangle and a 306 envelope on the plan.

On the drawings

  • Draw the 30-by-48-inch clear floor space at each element that needs one, and show whether the approach is forward or parallel.
  • If the space is in an alcove deeper than 24 inches (forward) or 15 inches (parallel), dimension the 36-inch or 60-inch alcove width.
  • For a forward approach under a lavatory or counter, section the knee and toe envelope: 17 to 25 inches of toe clearance below 9 inches, 11 inches of knee clearance at 9 inches tapering to 8 inches at 27 inches, and 30 inches of width.
  • Do not count under-fixture volume that fails 306 toward the clear floor space or the turning space.
  • Show one full unobstructed side of the clear floor space adjoining an accessible route or another clear floor space.

Run a free scan on your plans. A clear floor space that looks fine in plan, but loses its knee clearance in section, is the kind of comment the scan can surface before a reviewer does.

This is advisory. It is not a determination by the authority having jurisdiction. Confirm the adopted accessibility standard, its edition, and any local amendments before you change a drawing.