Check an accessible water closet in a toilet room, a wheelchair accessible compartment, or an ambulatory compartment against the 2010 ADA Standards: centerline, clear space, seat height, grab bars, dispenser, compartment door, toe clearance, and how many accessible compartments Section 213.3.1 requires.
Edition: 2010 ADA Standards for Accessible Design, Sections 213.3.1, 604.2 to 604.8, and 609.4 (U.S. Department of Justice). The IBC enforces ICC A117.1, whose dimensions can differ. Confirm the standard and edition the authority having jurisdiction enforces.
Clearance 60 in wide and 56 in deep minimum; water closet centerline 16 to 18 in from the side wall or partition.
| Check | Section | Result | Summary |
|---|---|---|---|
| Centerline from side wall | 2010 ADA Standards Section 604.2 | Pass | 18 in; required 16 to 18 in from the side wall or partition. |
| Clearance width (from side wall) | 2010 ADA Standards Section 604.3.1 | Pass | 60 in; required 60 in minimum. |
| Clearance depth (from rear wall) | 2010 ADA Standards Section 604.3.1 | Pass | 56 in; required 56 in minimum. |
Dimensions in inches; 1 in = 25.4 mm.
A single-user restroom, a floor-mounted stall, and a men's room with urinals.
A single-user restroom with the toilet 18 in from the side wall and a 60 by 56 in clear space meets 604.2 and 604.3.1, but a 42 in side grab bar mounted 10 in from the rear wall ends 52 in from it, short of the 54 in that 604.5.1 requires, so the layout fails. A wheelchair stall with a floor-mounted toilet needs 60 by 59 in, so a 57 in deep stall fails (it would pass with a wall-hung toilet). A men's room with 5 stalls and 2 urinals has 7 fixtures, so it needs 1 wheelchair stall and 1 ambulatory stall (213.3.1).
How the ADA Standards, the IBC, and A117.1 fit together is explained in the IBC vs. ADA vs. A117.1 guide. The 60-by-56-inch clearance is explained in the water closet clearance guide (ADA 604.3), and the 30-by-48-inch clear floor space and knee and toe envelope in the clear floor space guide (ADA 305 and 306). Fixture counts come from the plumbing fixture calculator, and restroom doors are checked in the door maneuvering clearance calculator. The adopted building code for a city is on its jurisdiction page.
Under 2010 ADA Standards Section 604.3.1 the clearance is 60 inches minimum measured perpendicular from the side wall and 56 inches minimum measured perpendicular from the rear wall. It may overlap the water closet, grab bars, dispensers, the accessible route, and the turning space, but no other fixture may be in it (604.3.2). The centerline of the water closet is 16 to 18 inches from the side wall or partition (604.2).
Section 604.8.1.1 requires 60 inches wide minimum, and 56 inches deep minimum with a wall-hung water closet or 59 inches deep minimum with a floor-mounted water closet. An ambulatory accessible compartment is 60 inches deep minimum and 35 to 37 inches wide (604.8.2.1), with the water closet centerline 17 to 19 inches from the side partition and grab bars on both sides.
The side wall bar is 42 inches long minimum, no more than 12 inches from the rear wall, and extends at least 54 inches from the rear wall (604.5.1). The rear wall bar is 36 inches long minimum and extends at least 12 inches on one side of the centerline and 24 inches on the other (604.5.2), or 24 inches centered where a recessed fixture leaves no room. Both are horizontal, 33 to 36 inches above the floor to the top of the gripping surface (609.4).
Section 213.3.1 requires at least one wheelchair accessible compartment where toilet compartments are provided, plus at least one ambulatory accessible compartment where six or more compartments are provided, or where water closets and urinals together total six or more fixtures.
This calculator uses the 2010 ADA Standards for Accessible Design. Buildings permitted under the IBC must also meet ICC A117.1 as referenced by the adopted code, and some states (California, for example) have their own accessibility codes. It is not a substitute for the code enforced by your authority having jurisdiction. See the jurisdiction pages for the edition a city has adopted, and scan the plan set before you rely on a result.
Values to check. (a) ICC A117.1 (2009, 2017) water closet and compartment dimensions were not encoded; they can differ from 2010 ADA 604, so check the A117.1 edition your code references. (b) Water closets and compartments for children's use (604.9 and its advisory table) are not calculated. (c) The rear grab bar recessed-fixture exception is checked as centered within 1/2 in; the flush-valve exception (split or shifted bar) is noted, not calculated. (d) Lavatory, urinal, and turning-space requirements (603, 605, 606, 304) and the grab bar cross section, spacing, and strength (609.2, 609.3, 609.8) are not calculated. (e) A dimension exactly equal to a minimum or maximum is treated as passing.