Door Maneuvering Clearance Calculator (2010 ADA 404.2.4)

Find the required maneuvering clearance at a door for each approach and side under 2010 ADA Standards Table 404.2.4.1 and 404.2.4.2, and check clear width, thresholds, hardware height, doors in series, opening force, and vision lights.

Edition: 2010 ADA Standards for Accessible Design, Section 404.2 (U.S. Department of Justice). The IBC enforces ICC A117.1, whose clearances can differ. Confirm the standard and edition the authority having jurisdiction enforces.

Measured parallel to the door, past the edge of the doorway.
Wall or casework within 18 in of the latch side, measured from the face of the door.
Face of the door to the stop, door open 90 degrees.
Openings more than 24 in deep need 36 in clear.
Pass · 2010 ADA Standards Table 404.2.4.1
60 × 18 in

60 in perpendicular to the doorway and 18 in beyond the latch side.

CheckSectionResultSummary
Maneuvering clearance2010 ADA Standards Table 404.2.4.1Pass60 in perpendicular, 18 in parallel; required 60 in perpendicular x 18 in beyond the latch side.
Extent of the clearance2010 ADA Standards Section 404.2.4NoteManeuvering clearances shall extend the full width of the doorway and the required latch side or hinge side clearance (Section 404.2.4). Entry doors to hospital patient rooms are not required to provide the clearance beyond the latch side (Exception).
Closer speed2010 ADA Standards Section 404.2.8.1NoteAdjust the closer so the door takes at least 5 seconds to move from 90 degrees open to 12 degrees from the latch.

Dimensions in inches; 1/2 in = 13 mm.

Worked example

An office door, a restroom door with a closer, and a hinge-side approach.

Approaching an office door from the front on the pull side needs 60 in perpendicular to the door and 18 in beyond the latch (Table 404.2.4.1), so a corridor that leaves 60 in by 16 in fails. On the push side of a restroom door with a closer and a latch, the clearance is 48 in by 12 in beyond the latch. Approaching from the hinge side on the pull side, either 60 in by 36 in or 54 in by 42 in works.

How this is calculated

  1. Choose the door type and approach. Pick a swinging door, a sliding or folding door, or a doorway without a door, and the direction of approach: front, hinge or pocket side, latch or stop side, or (doorways without doors) side.
  2. Pick the side and hardware. For swinging doors choose the pull or push side and whether the door has a closer and a latch, because Table 404.2.4.1 adds 6 or 12 inches in those cases.
  3. Read the required clearance. The calculator returns the minimum depth perpendicular to the doorway and the width beyond the latch or hinge side. Doorways without doors and sliding or folding doors use Table 404.2.4.2 only when they are less than 36 inches wide.
  4. Check recesses and the floor. An obstruction within 18 inches of the latch side that projects more than 8 inches beyond the door face requires the front approach clearance (404.2.4.3). The floor in the clearance is not steeper than 1:48 (404.2.4.4).
  5. Check the rest of the doorway. Enter the clear width, threshold height, hardware height, doors-in-series distance, opening force, and vision light height to check Sections 404.2.3 and 404.2.5 through 404.2.11.

How the ADA Standards, the IBC, and A117.1 fit together is explained in the IBC vs. ADA vs. A117.1 guide. Ramp slopes and accessible parking are in the accessible parking and ramp calculator. The adopted building code for a city is on its jurisdiction page.

FAQ

What is the required maneuvering clearance at the pull side of a door?

Under 2010 ADA Standards Table 404.2.4.1, a front approach to the pull side of a swinging door needs 60 inches perpendicular to the doorway and 18 inches parallel to it beyond the latch side. From the hinge side on the pull side, either 60 by 36 inches or 54 by 42 inches is required. From the latch side on the pull side, 48 by 24 inches is required, and the 48 inches becomes 54 inches if the door has a closer.

What clearance is needed on the push side of a door?

A front approach to the push side needs 48 inches perpendicular to the doorway and no clearance beyond the latch, but 12 inches beyond the latch side is added if the door has both a closer and a latch. From the hinge side, the push side needs 42 inches (48 with a closer and latch) by 22 inches beyond the hinge side. From the latch side, it needs 42 inches (48 with a closer) by 24 inches.

When does a recessed door need a front approach clearance?

Section 404.2.4.3 requires the forward approach clearance when any obstruction within 18 inches of the latch side of the doorway projects more than 8 inches beyond the face of the door, measured perpendicular to the door. This applies to doors recessed by thick walls, casework, or other fixed elements next to the doorway.

What other door requirements does Section 404.2 set?

Clear width is at least 32 inches (36 inches where the opening is more than 24 inches deep), measured between the door face and the stop with the door open 90 degrees. Thresholds are 1/2 inch high maximum (3/4 inch for existing beveled thresholds). Hardware is 34 to 48 inches above the floor. Doors in series are at least 48 inches apart plus the width of any door swinging into the space. Interior hinged and sliding or folding doors open with 5 pounds of force maximum, the floor in the clearance is not steeper than 1:48, and the bottom of at least one vision light is 43 inches maximum above the floor.

Check your full plan set →

This calculator uses the 2010 ADA Standards for Accessible Design. Buildings permitted under the IBC must also meet ICC A117.1 as referenced by the adopted code, and some states (California, for example) have their own accessibility codes. It is not a substitute for the code enforced by your authority having jurisdiction. See the jurisdiction pages for the edition a city has adopted, and scan the plan set before you rely on a result.

Values to check. (a) ICC A117.1 (2009, 2017) maneuvering clearances were not encoded; they can differ from Table 404.2.4.1, so check the A117.1 edition your code references. (b) The closer and latch adjustments follow the notes printed in the DOJ text version of Table 404.2.4.1; confirm against the printed table figure. (c) Clearances at automatic doors (404.3), hospital patient room doors (latch side exception), and dwelling-unit doors covered by other standards are not calculated. (d) A dimension exactly equal to the minimum is treated as passing.