2021 IECC wall insulation: the errata that changed the climate zone 4 and 5 row
R-15 continuous insulation over an empty cavity was in the printed table. The errata makes it R-20.
A wall section for a climate zone 5 house shows R-15 rigid foam outside the sheathing and nothing in the stud cavity. The note cites 2021 IECC Table R402.1.3, and the copy on the designer's desk agrees with it. The ICC errata for that table does not. In climate zones 4 and 5 the continuous-insulation-only option is now R-20, not R-15.
Two tables, one choice
2021 IECC Section R402.1.2 sets maximum assembly U-factors in Table R402.1.2. Section R402.1.3 makes Table R402.1.3, the insulation R-values, an alternative to those U-factors. Footnote a of Table R402.1.3 says R-values are minimums, and U-factors and SHGC are maximums.
The row that changed
The ICC errata for the 2021 IECC corrects Table R402.1.3 for all printings. It was posted August 10, 2021 and updated September 18, 2026. The wood frame wall column now reads:
- Climate zone 3: 20, or 13 plus 5ci, or 0 plus 15ci. Only the notation changed.
- Climate zone 4 except Marine, and 5 and Marine 4: 30, or 20 plus 5ci, or 13 plus 10ci, or 0 plus 20ci. The printed table read 20+5, 13+10ci, or 0+15. The errata adds "30 or" and changes the all-continuous option from 15 to 20.
- Climate zones 6, 7, and 8: 30, or 20 plus 5ci, or 13 plus 10ci, or 0 plus 20ci. The errata adds "30 or".
Footnote g says the first value is cavity insulation and the second is continuous insulation. "13&10ci" is R-13 in the cavity plus R-10 continuous. The same errata also extends footnote f, so in warm humid locations neither basement wall insulation nor crawl space wall insulation is required.
The free reader at codes.iccsafe.org, labeled Version Dec 2020, still prints the old wall row when we checked it today. If your reference is that page or a first printing, read the errata alongside it.
How the R-values count
Section R402.1.4 sets the arithmetic:
- Cavity insulation alone counts toward the cavity number. Layers in the cavity add up. Blown-in insulation uses the manufacturer's settled R-value.
- Continuous insulation alone counts toward the ci number. Layers of ci add up.
- Cavity R-value never counts toward the ci requirement.
- No R-value for other building materials or air films.
- Insulated siding used as continuous insulation is taken at its labeled R-value minus R-0.6.
In climate zone 4 or 5, R-13 cavity plus R-5 ci meets none of the four options. It is short on cavity for 20 plus 5ci and short on ci for 13 plus 10ci.
Two reductions that only work on the R-value path
- Section R402.2.1, ceilings with attics. Where the table requires R-49, R-38 over 100 percent of the ceiling area satisfies it wherever the full height of uncompressed R-38 extends over the wall top plate at the eaves. Where the table requires R-60, R-49 does the same. The reduction does not apply to Table R402.1.2 or the Total UA alternative in Section R402.1.5.
- Section R402.2.2, ceilings without attics. Where the table requires more than R-30 between the ceiling and the structural roof deck and the assembly does not have room for it, R-30 is the minimum, extended over the top of the wall plate without compression. That reduction is limited to 500 square feet or 20 percent of the total insulated ceiling area, whichever is less, and does not apply to the Total UA alternative.
Both depend on a detail. If the drawings claim R-49 for an R-60 ceiling, show the eave with the full-height insulation over the top plate.
Climate zone first
Section R301.1 assigns the climate zone from Figure R301.1 or Table R301.1, which lists counties. Section R301.2 says warm humid counties carry an asterisk. Two columns of Table R402.1.3 trip people up:
- Marine 4, climate zone 4C, uses the column labeled "5 and Marine 4", not "4 except Marine".
- Footnote e says there are no SHGC requirements in the Marine Zone.
The residential envelope calculator reads Table R402.1.3 with the errata applied, next to the Table R402.1.2 U-factors, for any climate zone.
What to put on the drawings
- The climate zone and the county you read it from, with the energy code edition.
- The compliance path. Section R401.2 offers the prescriptive option (R401.2.1), total building performance (R401.2.2), the Energy Rating Index (R401.2.3), or the tropical option (R401.2.4). Section R401.2.5 also requires additional energy efficiency. On the prescriptive path that is one of the Section R408.2 package options, and the option is identified on the R401.3 certificate.
- On each wall section: the cavity R-value and the continuous R-value as separate numbers, so a reviewer can check them against footnote g.
- The eave detail if you use the R402.2.1 reduction.
- Fenestration U-factor and SHGC on the window schedule.
The energy compliance documentation guide covers the forms, and the code adoption tracker and jurisdiction pages show which energy code a city enforces. States amend the IECC, and some write their own.
Run a free scan on the wall sections and the energy sheet together. A ci-only wall at R-15 in climate zone 5 is the kind of mismatch the scan can surface before a reviewer does.
This is advisory. It is not a determination by the authority having jurisdiction. Confirm the adopted edition and local amendments before you change a drawing.