Residential Envelope Calculator (2021 IECC Tables R402.1.2 and R402.1.3)

Prescriptive insulation minimum R-values, fenestration U-factor and SHGC, and the U-factor alternative, by IECC climate zone. Climate zone 4C uses the zone 5 column. Climate zone 3C stays with zone 3.

Edition: 2021 IECC Section R402.1, Tables R402.1.2 and R402.1.3. States amend the IECC. Washington uses the Washington State Energy Code, and Virginia amends the IECC. Confirm the energy code adopted by the authority having jurisdiction.

4C is Marine 4 and uses the zone 5 column. 3C uses the zone 3 column. Zones 7 and 8 share a column.
Leave this on all components, or read one row of the table.
Climate zone 4 except Marine (4A and 4B), 2021 IECC Section R402.1, Tables R402.1.2 and R402.1.3
ComponentTable R402.1.3Table R402.1.2
Fenestration U-factor0.300.30
Skylight U-factor0.550.55
Glazed fenestration SHGC0.400.40
Ceiling R-value600.024
Wood frame wall R-value30 or 20 & 5ci or 13 & 10ci or 0 & 20ci0.045
Mass wall R-value8/130.098
Floor R-value190.047
Basement wall R-value10ci or 130.059
Slab R-value and depth10ci, 4 ftNo slab column
Crawl space wall R-value10ci or 130.065

Ceiling R-value. Section R402.2.1 allows a lower ceiling R-value for an attic when the full height of uncompressed insulation extends over the wall top plate: R-38 may be used where Table R402.1.3 requires R-49, and R-49 may be used where it requires R-60. That reduction does not apply to the U-factor alternative in Section R402.1.2 or the Total UA alternative in Section R402.1.5. This calculator reports the tabulated values and does not apply the reduction.

Wood frame wall R-value. Any one of these meets the cell: R-30 cavity insulation; R-20 cavity insulation plus R-5 continuous insulation; R-13 cavity insulation plus R-10 continuous insulation; R-0 cavity insulation plus R-20 continuous insulation.

Wood frame wall R-value. Footnote g: the first value is cavity insulation and the value after "&" is continuous insulation. "13 & 5" means R-13 cavity insulation plus R-5 continuous insulation.

Mass wall R-value. The first value, R-8, applies when half or less of the insulation is on the interior of the mass wall. The second value, R-13, applies when more than half of the insulation is on the interior (footnote h, Section R402.2.5).

Mass wall R-value. Table R402.1.2 footnote b: when more than half the insulation is on the interior, the mass wall U-factor shall not exceed 0.087 (the tabulated U-factor is 0.098).

Basement wall R-value. Any one of these meets the cell: R-10 continuous insulation on the interior or exterior surface of the wall; R-13 cavity insulation on the interior side of the wall.

Basement wall R-value. Footnote c defines this notation. "10ci or 13" means R-10 continuous insulation on the interior or exterior, or R-13 cavity insulation on the interior. "15ci or 19 or 13 & 5ci" means R-15 continuous insulation, or R-19 cavity insulation on the interior, or R-13 cavity plus R-5 continuous.

Slab R-value and depth. Any one of these meets the cell: R-10 continuous insulation at the slab edge, extending 4 feet.

Slab R-value and depth. Footnote d: a heated slab also gets R-5 under the full slab area, in addition to the slab-edge R-value in the table. Slab-edge insulation for a heated slab does not have to extend below the slab. Table R402.1.2 has no slab U-factor column.

Crawl space wall R-value. Any one of these meets the cell: R-10 continuous insulation on the interior or exterior surface of the wall; R-13 cavity insulation on the interior side of the wall.

Crawl space wall R-value. Footnote c defines this notation. "10ci or 13" means R-10 continuous insulation on the interior or exterior, or R-13 cavity insulation on the interior. "15ci or 19 or 13 & 5ci" means R-15 continuous insulation, or R-19 cavity insulation on the interior, or R-13 cavity plus R-5 continuous.

R-values are minimums. U-factors and SHGC are maximums. NR means not required. ci means continuous insulation.

States amend the IECC. Washington uses the Washington State Energy Code. Virginia amends the IECC. Confirm the energy code enforced by the authority having jurisdiction.

The fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration, except the climate zone 0 through 3 skylight exception.

Worked example

Climate zone 2, climate zone 4 except Marine, climate zone 5, and Marine 4.

Climate zone 2 is ceiling R-49, wood frame wall 13 or 0 & 10ci, and fenestration U-factor 0.40. Climate zone 4 except Marine is ceiling R-60, wood frame wall 30 or 20 & 5ci or 13 & 10ci or 0 & 20ci, wood frame wall U-factor 0.045, and slab 10ci, 4 ft. Climate zone 5 is floor R-30, basement wall 15ci or 19 or 13 & 5ci, and SHGC 0.40. Marine 4 uses that same column, and footnote e changes the SHGC from the printed 0.40 to NR.

How this is calculated

  1. Identify the climate zone. Use IECC climate zones 0 through 8. Zone 4C, Marine 4, uses the "5 and Marine 4" column. Zone 3C uses the zone 3 column. Zones 7 and 8 share a column.
  2. Read Table R402.1.3. Read the prescriptive fenestration U-factor, skylight U-factor, glazed fenestration SHGC, ceiling R-value, wood frame wall R-value, mass wall R-value, floor R-value, basement wall R-value, slab R-value and depth, and crawl space wall R-value for that column.
  3. Read the U-factor alternative. Table R402.1.2 gives the maximum assembly U-factors and fenestration requirements for the same climate zone. There is no slab U-factor column. Assembly U-factors are maximums.
  4. Apply the footnotes that change a result. Footnote e removes the SHGC requirement in the Marine Zone. Footnote f can omit zone 3 basement and crawl space wall insulation in warm-humid locations. Footnote d adds R-5 under the full area of a heated slab. The 0.32 fenestration U-factor allowance applies only where the table marks it, for buildings above 4,000 feet or in windborne debris regions.
  5. Confirm the local energy code. States amend the IECC. Washington uses the Washington State Energy Code, and Virginia amends the IECC. Use the jurisdiction page for the edition the city enforces, then check the adopted text before you rely on a cell.

Commercial lighting power is a different table. See the lighting power and controls guide. The adopted energy code for a city is on its jurisdiction page.

FAQ

Which 2021 IECC tables set the residential envelope?

Section R402.1 sends the prescriptive path to Table R402.1.3 for insulation minimum R-values and fenestration requirements, and to Table R402.1.2 for maximum assembly U-factors and fenestration requirements. R-values are minimums. U-factors and SHGC are maximums. States amend the IECC. Washington uses the Washington State Energy Code, and Virginia amends the IECC. Confirm the energy code the authority having jurisdiction enforces.

Does Marine 4 use the same column as climate zone 4?

Marine 4 (climate zone 4C) uses the column labeled "5 and Marine 4". The column labeled "4 except Marine" is the one for climate zones 4A and 4B. Climate zone 3C stays with zone 3; the 2021 table does not give 3C its own column. Footnote e says there are no SHGC requirements in the Marine Zone, so a Marine 4 building does not take the 0.40 SHGC printed in the shared column.

What do the wall and slab notations mean?

The word "or" is a choice of assemblies, and any one of them meets the cell. "13 or 0 plus 10ci" means R-13 cavity insulation, or no cavity insulation plus R-10 continuous insulation. The printed table joins the cavity value and the continuous value with an ampersand. Footnote g says the first number is cavity insulation and the second is continuous insulation, so 13 plus 5 means R-13 cavity plus R-5 continuous. Footnote c says "10ci or 13" means R-10 continuous insulation on the interior or exterior of the wall, or R-13 cavity insulation on the interior side. "15ci or 19 or 13 plus 5ci" means R-15 continuous, or R-19 cavity on the interior, or R-13 cavity plus R-5 continuous. Slab depth is how far the edge insulation extends, as in "10ci, 2 ft" or "10ci, 4 ft".

Check your full plan set →

This calculator uses the 2021 International Energy Conservation Code model text, Section R402.1, Tables R402.1.2 and R402.1.3, for general reference. States amend the IECC. Washington uses the Washington State Energy Code, and Virginia amends the IECC. It is not a substitute for the energy code enforced by your authority having jurisdiction. See the jurisdiction pages for the edition a city has adopted, and scan the plan set before you rely on a result.

← All calculatorsBrowse guides →