IRC vs. IBC stair riser and tread: 7 3/4 and 10, or 7 and 11
Which code the building is under decides the stair. The exception inside the IBC is narrower than it looks.
A stair drawn at 7 3/4-inch risers and 10-inch treads is correct in a house and rejected in an office. Both numbers are real. They come from different codes, and the IBC carries a narrow copy of the residential numbers for a few occupancies only.
Which code the building is under
2021 IBC Section 101.2 has one exception: detached one- and two-family dwellings and townhouses not more than three stories above grade plane, with a separate means of egress, may comply with the IBC or the International Residential Code. IRC Section R101.2 states the same scope from the other side. Everything else, including apartments, is IBC.
The numbers, side by side
IRC, 2021. Section R311.7.5:
- R311.7.5.1: riser not more than 7 3/4 inches, measured between leading edges of adjacent treads. The section states a maximum only.
- R311.7.5.2: tread not less than 10 inches.
- R311.7.5.2.1: winders not less than 10 inches at the walkline and not less than 6 inches at any point within the clear width.
- R311.7.5.3: nosing projection 3/4 inch to 1 1/4 inches, not required where the tread is at least 11 inches.
- Dimensions exclude carpet, rugs, and runners. Open risers more than 30 inches above the floor below cannot pass a 4-inch sphere.
IBC, 2021. Section 1011.5.2:
- Riser 7 inches maximum and 4 inches minimum, measured between the nosings of adjacent treads.
- Rectangular tread 11 inches minimum.
- Winder treads are not permitted in means of egress stairways except within a dwelling unit (Section 1011.5.3).
- Section 1011.5.5: nosing curvature or bevel 1/16 to 9/16 inch, projection not more than 1 1/4 inches. Risers are solid, with an exception in 1011.5.5.3 for stairs that do not have to be accessible under Section 1009.3.
Both codes hold risers and treads within a flight to a 3/8-inch tolerance (IRC R311.7.5.1 and R311.7.5.2, IBC 1011.5.4).
The IBC exception that looks like the IRC
IBC Section 1011.5.2 Exception 3 allows a 7 3/4-inch maximum riser and a 10-inch minimum tread, 10-inch winders at the walkline, and 6-inch minimum winders. It applies in three places only:
- Group R-3 occupancies.
- Within dwelling units in Group R-2.
- Group U accessory to R-3, or accessory to individual R-2 dwelling units.
It also requires a 3/4-inch to 1 1/4-inch nosing on solid-riser stairs where the tread is under 11 inches. It does not reach an R-2 corridor stair, a lobby stair, or anything in Group B or M.
The 2024 IBC narrows it again. Exception 3 now covers dwelling units in R-2 "not required by Chapter 11 to be Accessible or Type A dwelling or sleeping units." An internal stair inside a Type A unit is back to 7 and 11 under 2024.
The 2024 IRC moved the section
In the 2024 IRC, means of egress is Section R318, so the riser is R318.7.5.1, the tread is R318.7.5.2, and nosings are R318.7.5.3. The dimensions did not change. A code sheet citing R311.7.5 on a 2024 IRC project points at the wrong section, which is a small comment and an avoidable one. Check which edition the city adopted on the code adoption tracker or the jurisdictions page.
What the difference costs on a 9-foot floor
Arithmetic for a 108-inch floor-to-floor rise, straight run:
- At a 7-inch maximum: 108 / 7 = 15.4, so 16 risers at 6 3/4 inches, 15 treads at 11 inches, 165 inches of run.
- At a 7 3/4-inch maximum: 108 / 7.75 = 13.9, so 14 risers at about 7 23/32 inches, 13 treads at 10 inches, 130 inches of run.
That is close to three feet of plan. A stair laid out at residential numbers in a building that does not qualify will not fit when it is corrected. The stair geometry calculator runs both IBC cases. Pick "General" for 7 and 11, or the R-3 / R-2 dwelling unit / accessory U rule for 7 3/4 and 10. It does not calculate winders, and it is the IBC, not the IRC. Width, landings, headroom, and handrails are in the stairway requirements guide and the handrails and guards guide. Open stairs between floors are the exit access stairways guide.
What to put on the drawings
- On the code sheet: which code governs (IRC or IBC), the edition, and the occupancy group.
- On the stair section: riser count and height, tread depth, nosing projection, and the total rise and run.
- If you use IBC Exception 3, name it, and name the R-3, R-2 dwelling unit, or accessory U condition that qualifies.
Upload the stair sections with the code sheet and run a free scan. A 10-inch tread under a Group B code sheet is a mismatch the scan can surface before the reviewer does.
This is advisory. It is not a determination by the authority having jurisdiction. State residential codes and local amendments change these numbers and section numbers. Confirm the adopted edition before you change a drawing.