Exit Access Stairways: When the IBC Lets the Stair Stay Open

Last reviewed November 12, 2026. Citations are to the 2021 model codes unless a section says otherwise. Confirm the adopted edition on the jurisdictions page before you rely on a number.

The short answer: An open stair between floors is an exit access stairway, not an exit. Under the 2021 IBC, §1019.3 requires floor openings that contain exit access stairways or ramps, in occupancies other than Groups I-2 and I-3, to be enclosed in a shaft complying with §713 — unless the opening fits one of the exceptions. The two that cover ordinary buildings are the two-story exception, and the sprinklered opening protected with a draft curtain and closely spaced sprinklers. Stair geometry is a separate check, in §1011.

Exit access stair versus exit stair

An interior exit stairway is part of the exit. Once an occupant is inside it, the enclosure has to protect them until exit discharge. An exit access stairway is still exit access. Occupants using it have not yet reached an exit, so travel distance and the number of stories they may pass through are still running. The means of egress guide is the map of those three pieces. The stairway guide is riser, tread, width, and headroom. This page is only the enclosure question, which is the one that decides whether the architectural feature in the lobby can stay open.

Groups I-2 and I-3 are outside §1019.3. Their exit access stairs are enclosed under §1019.4. Do not use the two-story exception in a hospital.

Code anchor — 2021 IBC §1019.3

The section text is in 2021 IBC Chapter 10. If none of the exceptions apply, the opening is a shaft under §713. Section 713.4 rates that shaft at 2 hours where it connects four or more stories, and 1 hour where it connects three or fewer, and not less than a floor assembly it penetrates when that floor is required to be 2 hours or more. The door in that shaft comes from Table 716.1(2): 1-1/2 hours in a 2-hour shaft, 1 hour in a 1-hour shaft enclosure.

Exceptions designers actually use:

  • Exception 1 — two stories. The stair or ramp serves, or atmospherically communicates between, only two adjacent stories, and those interconnected stories are not open to other stories. A two-story office with a communicating lobby fits. A three-story atrium that is open at each level does not fit this exception, even if each run of stair only touches two landings.
  • Exception 2 — inside a dwelling or sleeping unit. In Group R-1, R-2, or R-3, an exit access stair connecting four stories or fewer may be open when it serves and is contained within a single dwelling unit, sleeping unit, or live/work unit.
  • Exception 4 — sprinklered opening. The building is sprinklered throughout under §903.3.1.1 (NFPA 13). The area of the vertical opening between stories does not exceed twice the horizontal projected area of the stairway or ramp. The opening is protected by a draft curtain and closely spaced sprinklers in accordance with NFPA 13. In occupancies other than Group B and M, the opening may not connect more than four stories. Groups B and M are not subject to that four-story cap.
  • Exception 5 — atrium. The stair is inside an atrium that complies with §404. An open stair in a hole through the floor is not an atrium until the smoke control, enclosure, and use rules of §404 are met.

Further exceptions cover open parking garages, smoke-protected or open-air assembly seating, the stair from a balcony or press box to the assembly floor, and exterior exit access stairs between occupied roofs. Read the list before you rely on one that is not summarized here. ICC’s 2021 means-of-egress training describes Exception 4 the same way: draft curtain and closely spaced sprinklers, four-story limit outside Groups B and M.

The stair can be open and the egress path can still fail

Leaving the shaft off the stair does not end the review. Exit access travel distance in Table 1017.2 is measured along the open stair. The path of egress travel to an exit is limited in how many stories it may pass through; the code’s general rule is not more than one adjacent story, with its own exceptions. A rated corridor that reaches the open stair has to keep its rating along that path under §1020.7. And the stair still needs the geometry, handrails, and guards in §1011, §1014, and §1015.

Takeaways

  • Label the stair “exit access” or “exit” on the life-safety plan. The enclosure rules are different.
  • Two stories, not open to a third, is the clean exception. Dimension nothing else and you are usually done.
  • The decorative open stair in a sprinklered building still needs the draft curtain, the closely spaced sprinklers, and the area limit of twice the stair’s footprint.
  • If you enclose it, rate the shaft from §713.4 and the door from Table 716.1(2). Do not invent a 1-hour enclosure for a stair that connects four stories.

Common mistakes

  • Calling an open stair an exit because it discharges near the lobby door. If it is not enclosed as an exit, occupants are still in exit access.
  • Using Exception 1 on a three-story communicating volume by arguing that each flight only connects two floors. The stories are open to other stories, so the exception does not apply.
  • Claiming Exception 4 with an NFPA 13R system, or without the draft curtain. The section names §903.3.1.1 and NFPA 13 protection of the opening.
  • Forgetting the door swing and hardware once the stair is enclosed and the occupant load exceeds 49. See door swing and panic hardware.