Last reviewed November 12, 2026. Citations are to the 2021 model codes unless a section says otherwise. Confirm the adopted edition on the jurisdictions page before you rely on a number.
Reviewers write two corridor comments that look alike and are not. One is width and capacity, in §1020.3 and the width guide. The other is whether the walls have a fire-resistance rating at all. A sprinklered office can have a 0-hour corridor that is still too narrow, and an unsprinklered office can have a 44-inch corridor that is still required to be 1 hour. Check both.
Section 1020.2 says corridors are fire-resistance rated in accordance with Table 1020.2, and that walls required to be rated comply with §708 for fire partitions. The chapter text is in the 2021 IBC Chapter 10.
“Greater than 30” means the row does not apply at 30 or fewer. “Not permitted” in the unsprinklered column means that occupancy is not allowed to omit the sprinkler system the table is relying on. Footnotes change Group R and the institutional rows. Read them in the adopted code. The model table:
| Occupancy | Occupant load served | Without sprinklers | With sprinklers |
|---|---|---|---|
| H-1, H-2, H-3 | All | Not permitted | 1 hour |
| H-4, H-5 | Greater than 30 | Not permitted | 1 hour |
| A, B, E, F, M, S, U | Greater than 30 | 1 hour | 0 hours |
| R | Greater than 10 | Not permitted | 0.5 hour, or 1 hour |
| I-2 | All | Not permitted | 0 hours |
| I-1, I-3 | All | Not permitted | 1 hour |
| I-4 | All | 1 hour | 0 hours |
The sprinkler column is not “any sprinklers.” For the rows marked in the model footnotes, the building is equipped throughout with a system in accordance with §903.3.1.1 or §903.3.1.2 where that system is allowed. For Group R, the 0.5-hour value is the ordinary sprinkler case, and the 1-hour value is the footnote for Group R-3 and R-4 buildings sprinklered under §903.3.1.3 (NFPA 13D). Confirm the footnote letters in your printing. Many summaries still show an unsprinklered Group R corridor as 1 hour. The 2021 table says “Not permitted” in that cell, because new Group R buildings are sprinklered under §903.2.8.
A 0-hour result for Group I-2 does not mean the corridor walls disappear. The table footnote sends you to §407.2 and §407.3. Those sections still regulate how an I-2 corridor is built. A 0 in the fire-resistance column is not a note that says “no separation.”
Section 1020.2 lists exceptions. The ones that show up on ordinary plans:
Section 1020.7 requires a fire-resistance-rated corridor to be continuous from the point of entry to an exit, and not interrupted by intervening rooms. Foyers, lobbies, or reception rooms constructed as required for corridors are not treated as intervening rooms. If the path includes an unenclosed exit access stairway, the rating has to continue for the length of that stairway and the connecting corridor on the adjacent floor. See exit access stairways before you leave a rated corridor open to a communicating stair.
Doors in a rated corridor take their fire-protection rating from Table 716.1(2). For corridor fire partitions, that table calls for a 20-minute (1/3-hour) door in both the 1-hour and the 0.5-hour corridor wall. A 45-minute door is the “other fire partition” number, and it is the wrong default for a corridor. The door also has to be self- or automatic-closing as the opening-protective section requires. Penetrations of the rated wall are a separate comment, covered in the firestopping guide.
This guide describes the model code for general understanding and is not a substitute for the adopted code and amendments enforced by your local authority having jurisdiction. Verify all figures against your jurisdiction's codes of record.