Fire Door Ratings Under IBC Table 716.1(2)

Last reviewed November 12, 2026. Citations are to the 2021 model codes unless a section says otherwise. Confirm the adopted edition on the jurisdictions page before you rely on a number.

The short answer: The door does not inherit the wall’s hourly rating. The 2021 IBC assigns a fire-protection rating in Table 716.1(2), and it depends on what the wall is, not only on how many hours it is. A 2-hour shaft or interior exit stairway takes a 1-1/2-hour door. A 1-hour shaft, exit enclosure, or exit passageway takes a 1-hour door. A 1-hour fire barrier used for other separations takes a 3/4-hour door. A corridor fire partition takes a 20-minute (1/3-hour) door, whether the wall is 1 hour or 1/2 hour. Specifying “90-minute doors at all rated walls” fails the corridor and over-specifies nothing the reviewer asked you to prove.

Opening protective, not a small piece of wall

Section 716.1 requires opening protectives required by other sections to comply with Section 716 and to be installed in accordance with NFPA 80. Fire door assemblies are tested to NFPA 252 or UL 10C for side-hinged and pivoted doors (§716.2.1.1). The rating you put in the door schedule is the minimum fire door and fire shutter assembly rating from Table 716.1(2). Glazing in the door, and sidelights and transoms, have their own columns in that table and are often more restrictive than the door leaf. A 45-minute door with an untested sidelight still fails.

The overview of wall types is in the fire-resistance-rated construction guide. This page is what happens at the opening. Read Table 716.1(2) in the 2021 IBC Chapter 7. The pairings below are the ones that generate comments. The table has more rows for fire walls, double fire walls, exterior walls, and horizontal exits, plus vision-panel size limits. Use the row that names your assembly.

Code anchor — the pairings reviewers check

  • Fire walls and fire barriers rated more than 1 hour. A 4-hour or 3-hour wall takes a 3-hour door. A 2-hour wall takes a 1-1/2-hour door. A 1-1/2-hour wall takes a 1-1/2-hour door. Note d allows two 1-1/2-hour doors, one on each side of the same opening in a fire wall, to count as one 3-hour door.
  • Shafts, interior exit stairways, and interior exit ramps, 2 hours. 1-1/2-hour door. Shaft rating itself is §713.4: 2 hours when the shaft connects four or more stories, 1 hour when it connects three or fewer, and not less than the floor it penetrates when that floor is 2 hours or more.
  • 1-hour fire barriers that enclose shafts, exit access stairs or ramps, interior exit stairs or ramps, and exit passageways. 1-hour door.
  • Other 1-hour fire barriers. 3/4-hour door. This is the row for many incidental-use and occupancy separations.
  • Corridor fire partitions. 1/3 hour (20 minutes), for both a 1-hour corridor wall and a 0.5-hour corridor wall. See when the corridor is rated.
  • Other fire partitions. 3/4 hour in a 1-hour wall, and 1/3 hour in a 0.5-hour wall. Footnote i says two 20-minute doors, installed on opposite sides of the same opening in a fire partition, are equivalent to one 45-minute door. That footnote is not a license to use a single 20-minute door in a dwelling-unit separation.
  • Smoke barriers, 1 hour. 1/3-hour door, with the glazing limits in the smoke-barrier row.

Fire-protection-rated glazing is marked differently from fire-resistance-rated glazing. Table 716.1(1) is the marking key: “D” for fire-door criteria, “H” for the hose stream, “T” for the temperature-rise limit, “OH” for fire-window criteria, and “W” for glazing that meets wall criteria under ASTM E119 or UL 263. A vision panel that exceeds the square-inch limit in Table 716.1(2) has to be the glazing the table allows at that larger size, which is often fire-resistance-rated glazing rather than fire-protection-rated glazing.

What else the schedule has to show

  • Closer. A fire door that is propped open, or specified without a closer, does not provide the rating. Automatic-closing on smoke detection is allowed only where the section you are using permits it, including the smoke-resistant incidental-use door in §509.4.2.
  • Hardware on an egress fire door. If the door is also on the means of egress, panic hardware has to be fire exit hardware, listed to UL 10C and UL 305. See door swing and panic hardware.
  • Label. The review comment “provide rated assembly” is asking for a listed assembly, installed as tested, under NFPA 80. A note that says “90 min” with no listing basis is not a specification.

Takeaways

  • Identify the wall type first: fire wall, fire barrier, shaft, exit enclosure, corridor fire partition, other fire partition, or smoke barrier.
  • Then read the door column. Hour-for-hour matching is not the table.
  • Check the vision panel and the sidelight before you draw a full-lite door in a stair enclosure.
  • Twenty minutes is the corridor number. Forty-five minutes is the other-fire-barrier and other-fire-partition number. Ninety minutes is the 2-hour shaft and 2-hour fire-barrier number.

Common mistakes

  • A 20-minute door in a 1-hour occupancy separation or incidental-use barrier. That door belongs in a corridor fire partition.
  • A 60-minute door in a 1-hour exit stair when the stair connects enough stories to be a 2-hour shaft. The door went up with the wall, to 90 minutes.
  • Ignoring footnote h, which does not allow fire-protection-rated glazing in fire barriers required by IFC Section 1207 to enclose energy storage systems. Those openings need fire-resistance-rated glazing tested to ASTM E119 or UL 263 where glazing is used at all.
  • Copying the door rating into the damper and penetration notes. Ducts and pipes are dampers and firestopping, not door ratings.

Related checks

This guide describes the model code for general understanding and is not a substitute for the adopted code and amendments enforced by your local authority having jurisdiction. Verify all figures against your jurisdiction's codes of record.