Last reviewed November 12, 2026. Citations are to the 2021 model codes unless a section says otherwise. Confirm the adopted edition on the jurisdictions page before you rely on a number.
A through penetration breaches both sides of the assembly. A membrane penetration breaches one side — a back-box, a recessed cabinet, a pipe that stops inside the wall. Section 714 treats them separately because the test is different. Joints between two rated assemblies, including the head-of-wall joint, are Section 715, tested to ASTM E1966 or UL 2079. They are not a penetration firestop. Ducts that need a damper are a third detail. See the fire and smoke damper guide before you firestop a duct opening that was supposed to receive a damper, or the reverse.
The wall types that arrive at Section 714 are the ones in the Chapter 7 guide: fire walls, fire barriers, smoke barriers, and fire partitions. If the wall is not required to be rated, this section is not what creates the firestop. If it is rated, every pipe, conduit, cable, and box is in play.
Section 714.4.1.2 requires the through-penetration firestop system to be installed as tested in accordance with ASTM E814 or UL 1479, at a minimum positive pressure differential of 0.01 inch of water, and to have an F rating not less than the required fire-resistance rating of the wall. The F rating is the time the system limits the passage of fire. The T rating is the time it also limits temperature rise. The general through-penetration rule quoted here demands the F rating. Do not assume a T rating unless the section you are in asks for one. Membrane penetrations by boxes other than electrical boxes, under the §714.4.2 exceptions, are one place the code does ask for both an F rating and a T rating equal to the wall.
ICC’s inspection guidance for the 2021 IBC describes the same three legal paths: the penetration was tested as part of the original wall assembly, it is protected by a listed penetration firestop system, or it fits an exception in §714.4.1 or §714.4.2. Reviewers accept a system number that matches the wall and the penetrant. They do not accept a product data sheet for a caulk that was tested in a concrete wall when the project wall is gypsum studs.
The annular-space exception in §714.4.1 is narrow. Where the penetrant is steel, ferrous, or copper pipe, tube, or conduit, the code allows concrete, grout, or mortar in a concrete or masonry wall when the penetrant is a maximum 6-inch nominal diameter and the opening does not exceed 144 square inches, installed the full thickness required to maintain the rating. A second exception allows a fill material shown to keep flame and hot gases from igniting cotton waste under ASTM E119 or UL 263 conditions for the full rating period. Neither exception is “seal the stud wall with mortar.”
Section 714.4.2 requires membrane penetrations to comply with the through-penetration rules, and then lists exceptions. The one that covers ordinary steel electrical boxes is specific: maximum 2-hour walls, steel boxes not over 16 square inches, aggregate openings not over 100 square inches in any 100 square feet of wall, and an annular space around the box not over 1/8 inch. Boxes on opposite sides of the wall have to be separated — by at least 24 inches where the stud cavities do not communicate, or by a listed method such as putty pads, fireblocking, or the separation distance in the listing. Larger steel boxes, and boxes that blow past the aggregate area, fall under a further exception that requires listed putty pads or another listed method.
Plastic boxes are not in the steel-box exception. They have to be listed for use in the rated assembly and installed as that listing says. A sprinkler pipe has its own small exception: the annular space may be covered by a metal escutcheon plate. That sentence does not cover a plumbing stack.
Section 715.4 is the related detail at the curtain wall: the void at a fire-resistance-rated floor and an exterior curtain wall is a perimeter fire containment system tested to ASTM E2307, with an F rating not less than the floor. Calling that joint “firestopping” and pointing at a through-penetration listing is a different comment, and a common one on the floor-edge detail.
This guide describes the model code for general understanding and is not a substitute for the adopted code and amendments enforced by your local authority having jurisdiction. Verify all figures against your jurisdiction's codes of record.