Riser count and height, tread count and total run, flights and landings, minimum width, and headroom for a straight stair under 2021 IBC Section 1011.
Edition: 2021 IBC model text, Sections 1011.2, 1011.3, 1011.5.2, 1011.5.4, 1011.6, and 1011.8. Straight flights only; winders, curved, spiral, and stepped-aisle stairs are not calculated.
2021 IBC Section 1011.5.2: 7 in maximum, 4 in minimum. Fewest risers allowed: 21. Riser height complies.
Tread 11 in (minimum 11 in). 1 flight, 0 intermediate landings; the run excludes landings.
Minimum width 44 in (2021 IBC Section 1011.2). Landing depth at least 44 in (2021 IBC Section 1011.6). Headroom at least 80 in (2021 IBC Section 1011.3). Risers and treads in a flight may vary by no more than 3/8 in (2021 IBC Section 1011.5.4).
A 12 foot (144 inch) floor-to-floor stair in a business occupancy, and the same method at 14 feet and in a dwelling unit.
144 in divided by the 7 in maximum is 20.6, so the stair needs 21 risers of 6 7/8 in. One flight has 20 treads, and at 11 in each the run is 220 in. At 168 in the stair needs 24 risers of 7 in; one flight can hold at most 20 of them within 144 in, so it splits into 2 flights with 1 intermediate landing and 22 treads. In a Group R-3 dwelling with a 108 in rise, Exception 3 gives 14 risers of 7 11/16 in and 13 treads of 10 in.
Required capacity can make a stair wider than the minimum; use the egress width calculator for the Section 1005.3.1 factor. The exit access stairways guide covers enclosure and opening rules that this page does not.
Section 1011.5.2 sets risers at 7 inches maximum and 4 inches minimum, and rectangular treads at 11 inches minimum. Exception 3 allows a 7 3/4 inch maximum riser and a 10 inch minimum tread in Group R-3, within Group R-2 dwelling units, and in Group U accessory to those. Local amendments vary, so check the jurisdiction page for the adopted edition.
Divide the floor-to-floor rise by the maximum riser height and round up. A 144 inch rise at 7 inches maximum needs 21 risers of about 6 7/8 inches. Section 1011.5.4 limits the difference between the largest and smallest riser in a flight to 3/8 inch, so the risers are drawn equal.
Section 1011.8 limits a flight to 12 feet (144 inches) of vertical rise between floor levels or landings. Section 1011.6 makes each landing at least as wide as the stair and at least as deep as the stair width or 48 inches, whichever is less.
This calculator uses the 2021 International Building Code model text for general reference. Local amendments vary. It is not a substitute for the adopted code enforced by your authority having jurisdiction. See the jurisdiction pages for the edition a city has adopted, and scan the plan set before you rely on a result. A cell marked provisional was not confirmed from the model-code text and should not be used until you check the printed table.