2 percent Type A above 20 units per site. Every unit Type B from four units per structure. Then the exceptions.

InstaPreView · Published November 16, 2026 · Updated November 16, 2026
Line drawing of a tenant floor plan with demising walls and one suite outlined, titled “Type A vs Type B units: how many your apartment building needs”. InstaPreView by Byts & Bytes.

A 120-unit apartment building with elevators has two counts on its accessibility sheet: how many Type A units, and how many Type B units. Designers often get the first count right and miss the second, because the second one is almost always "all of them."

This post walks through the 2021 IBC scoping for Group R-2 apartment houses. The technical design of each unit type is in ICC A117.1, Chapter 11. The IBC decides how many of each you need.

Three unit types, three levels

2021 IBC Section 1108.2 says units required to be Accessible units, Type A units, or Type B units shall comply with the applicable portions of Chapter 11 of ICC A117.1. It also sets an order. A required Type A unit may be built as an Accessible unit. A required Type B unit may be built as an Accessible unit or a Type A unit. Going the other way is not allowed.

Note the numbering. In the 2021 IBC, dwelling and sleeping unit scoping is Section 1108. Section 1107 in that edition covers electric vehicle charging stations and fuel-dispensing systems. Check the section numbers in the edition your jurisdiction adopted before you cite them on a sheet.

Type A: 2 percent, above 20 units

Section 1108.6.2.2.1 applies to Group R-2 apartment houses, monasteries, and convents:

  • Where the R-2 occupancy contains more than 20 dwelling or sleeping units, at least 2 percent, and not less than one, must be Type A units.
  • All Group R-2 units on the site count toward the total, not one building at a time.
  • Type A units have to be dispersed among the various classes of units.
  • Existing structures on the site do not count toward the total.

For 120 units, 2 percent is 2.4, so at least 3 Type A units. For a 20-unit building, there is no Type A requirement under this section, since the trigger is more than 20.

Type B: every unit, from four units up

Section 1108.6.2.2.2 says that where there are four or more dwelling or sleeping units intended to be occupied as a residence in a single structure, every one of those units shall be a Type B unit. The Type A count does not replace this. A unit built to Type A satisfies the Type B requirement for that unit, which is what the hierarchy in 1108.2 allows.

The four-unit trigger is per structure, while the Type A count is per site. A site with five fourplexes has 20 units: no Type A units are required, but every unit in every fourplex is scoped for Type B, subject to the exceptions below.

The exceptions that reduce Type B counts

Section 1108.7 lets you reduce the number of Type A and Type B units where Section 1108.5 or 1108.6 allows it. For apartment houses, both counts can use it:

  • No elevator (1108.7.1): only units on certain stories are required. At least one story with units needs an accessible entrance from the exterior, and all units on that story are Type B. Other stories are added when their entrances are near arrival points and the slopes within 50 feet are 10 percent or less (undisturbed site or planned finished grade).
  • Multistory units (1108.7.2): a multistory unit without elevator service is not required to be Type B. Where an external elevator serves only one floor of the unit, that floor is the primary entry and must meet Type B, with a living area, kitchen, and toilet facility on that floor where the unit has them.
  • Elevator to the lowest residential story only (1108.7.3): only units on that story are required to be Type B.
  • Site impracticality (1108.7.4): on a site with multiple nonelevator buildings, the count can drop to the percentage of the site with pre-development grades under 10 percent, with a floor of 20 percent and other conditions.
  • Flood hazard areas (1108.7.5): nonelevator buildings where the required floor elevation creates more than 30 inches of rise, and a slope over 10 percent, to arrival points within 50 feet are exempt.

Sections 1108.7.1, 1108.7.4, and 1108.7.5 are written for buildings without elevator service. In an elevator building, the only reduction in this list is 1108.7.3, and only where the elevator serves just the lowest residential story.

Spaces the units share

Section 1108.3 says rooms and spaces available to the public or to residents and serving Accessible, Type A, or Type B units must be accessible, including toilet and bathing rooms, kitchens, living and dining areas, and exterior spaces such as patios, terraces, and balconies. Section 1108.4 requires at least one accessible route connecting accessible building entrances with the primary entrance of each of those units and with the spaces that serve them.

What to put on the accessibility sheet

  • Total Group R-2 units on the site, and the Type A count with the 2 percent math shown.
  • Where the Type A units are, and how they are dispersed among unit types.
  • The Type B count per structure, and any 1108.7 exception you used, with the slope data that supports it.
  • The A117.1 edition the jurisdiction references for unit design.

For the broader picture, see the accessibility guide, accessible routes, and accessible parking; the accessible parking calculator handles the space count. States and cities amend Chapter 11, so check the code adoption tracker and your jurisdiction page. Federal fair housing and ADA requirements apply on their own terms and are not covered here.

Run a free scan on a multifamily set. A unit matrix that lists Type A units but never states the Type B count is a common comment the scan can surface before a reviewer does.

This is advisory. It is not a determination by the authority having jurisdiction. Confirm the adopted edition and local amendments before you change a drawing.