When one exit is enough: IBC 1006.3.4 single-exit stories
A first story can have one exit with up to 49 occupants and 75 feet of travel. How the 2021 IBC single-exit tables work, and where they stop.
A designer lays out a two-story office building with one stair. The ground floor has 45 occupants and the second floor has 35. The reviewer's comment: "Second story occupant load exceeds 29. Provide a second exit (IBC Table 1006.3.4(2))." The first floor was fine. The second floor needs another stair.
The rule behind that comment is IBC Section 1006.3.4, which lists when a story can be served by a single exit. This post walks through it in the 2021 IBC, with a note at the end on what the 2024 IBC changed.
Start with Table 1006.3.3
Every story and occupied roof starts at two exits. Table 1006.3.3 sets the minimum by occupant load per story:
- 1 to 500 occupants: 2 exits or access to exits
- 501 to 1,000: 3
- More than 1,000: 4
Section 1006.3.3 then says: "A single exit or access to a single exit shall be permitted in accordance with Section 1006.3.4." So a single exit is an exception you have to qualify for, not the default.
The five ways to qualify
Section 1006.3.4 permits a single exit from any story or occupied roof where one of these conditions exists:
- "The occupant load, number of dwelling units and exit access travel distance do not exceed the values in Table 1006.3.4(1) or 1006.3.4(2)."
- Rooms, areas and spaces complying with Section 1006.2.1 whose exits discharge directly to the exterior at the level of exit discharge.
- Parking garages where vehicles are mechanically parked.
- Group R-3 and R-4 occupancies.
- Individual single-story or multistory dwelling units, when the unit complies with Section 1006.2.1 as a space with one means of egress and either its exit discharges directly to the exterior at the level of exit discharge or the exit access outside its entrance door reaches at least two approved independent exits.
Most commercial projects use condition 1, so the rest of this post is about the two tables.
Table 1006.3.4(2): stories for most occupancies
First story above or below grade plane
- Groups A, B, E, F, M, and U: up to 49 occupants, 75 feet of exit access travel distance
- Groups H-2 and H-3: 3 occupants, 25 feet
- Groups H-4, H-5, I, R-1, and R-2 sleeping units: 10 occupants, 75 feet
- Group S: 29 occupants, 75 feet
Second story above grade plane
- Groups B, F, M, and S: up to 29 occupants, 75 feet
Third story above grade plane and higher: not permitted.
Footnote b raises the travel distance for Groups B, F, and S to 100 feet "in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1." Footnote d limits exit access travel distance in a Group S-2 open parking garage to 100 feet. Footnote a requires R-2 buildings to be sprinklered throughout under 903.3.1.1 or 903.3.1.2 and to have emergency escape and rescue openings under Section 1031.
Only Groups B, F, M, and S appear on the second-story row. A Group A or E space on a second story cannot use condition 1, however small its occupant load.
Table 1006.3.4(1): R-2 dwelling units
For Group R-2 occupancies made up of dwelling units, a basement, first, second, or third story above grade plane may have one exit with up to 4 dwelling units and a maximum exit access travel distance of 125 feet. The fourth story and higher is not permitted. The same footnote a applies: sprinklered throughout under 903.3.1.1 or 903.3.1.2, with emergency escape and rescue openings under Section 1031. R-2 sleeping units, such as a dormitory, use Table 1006.3.4(2) instead.
Mixed occupancies on one story
Section 1006.3.4.1 lets a story with more than one occupancy keep a single exit if each occupancy meets its own row and "the sum of the ratios of the calculated number of occupants of the space divided by the allowable number of occupants indicated in Table 1006.3.4(2) for each occupancy does not exceed one." Where dwelling units share the story, "the actual number of dwelling units divided by four plus the ratio from the other occupancy" must not exceed one.
A first story with a 30-occupant office (Group B, 49 allowed) and a 15-occupant shop (Group M, 49 allowed) works out to 30/49 + 15/49 = 0.92. One exit is still permitted if the travel distance also works. Add a 10-occupant storage area (Group S, 29 allowed) and the sum is 0.92 + 0.34 = 1.26, so the story needs two exits.
Four quick checks
- Two-story office, no sprinklers. First story 45 occupants with 70 feet of travel: one exit is permitted (49 and 75). Second story 35 occupants: over 29, so two exits are required.
- Same second story at 25 occupants with 90 feet of travel. Over 75 feet without sprinklers. In a building sprinklered throughout under 903.3.1.1, footnote b allows 100 feet, so one exit works.
- Ground-floor restaurant with 60 occupants. Group A over 49, so Table 1006.3.3 applies and the story needs two exits.
- Three-story apartment building with four dwelling units per story, sprinklered with emergency escape and rescue openings and 110 feet of travel: one exit is permitted on each story. A fourth story is not.
Story exits are not room exits
Section 1006.3.4 is about stories and occupied roofs. Whether a room or space inside the story can have one exit access doorway is a separate check under Section 1006.2.1 and its table, which sets its own occupant load and common path limits. A single-exit story can still have a room that needs two doors, and a story that needs two exits can be full of rooms with one door each. Our number and arrangement of exits guide and travel distance and common path guide cover the space-level rules.
What the 2024 IBC changed
We read Section 1006.3.4 in the 2024 IBC as well. The occupant loads, dwelling unit counts, and travel distances are the same. The 2024 text says "occupiable roof" instead of "occupied roof." It adds occupiable roofs over the first story to the first-story row of Table 1006.3.4(2), and occupiable roofs over the first or second story to Table 1006.3.4(1) when the roof is reached through and serves individual dwelling units. Footnote b's 100 feet now also covers an occupiable roof of a sprinklered B, F, or S building.
Check your numbers
The required exits and exit separation calculator applies Table 1006.3.3 and the Section 1006.3.4 single-exit check to a story, then the Section 1007.1.1 separation between exits. Feed it the occupant load from the occupant load calculator. If your jurisdiction is still on a 2015-based code, the business factor is 100 gross, not 150, which can push a second story over 29. See business occupant load: 100 gross vs. 150 gross.
States and cities amend Chapter 10. Check your jurisdiction page and the code adoption tracker for the adopted edition before you rely on these numbers.
Run a free scan on your egress plan. A single-exit story that is over its occupant load or travel distance is a comment the scan can flag before a reviewer does.
This is advisory. It is not a determination by the authority having jurisdiction. Confirm the adopted edition and local amendments before you change a drawing.