Minimum exits from 2021 IBC Table 1006.3.3, single-exit stories from Section 1006.3.4, and the one-half or one-third diagonal separation in Section 1007.1.1.
Edition: 2021 IBC model text. The occupant-load table for a story is Table 1006.3.3. Section 1006.3.4 is the single-exit allowance.
2021 IBC Table 1006.3.3. Table minimum before the single-exit check: 3.
Required separation: 50 ft (one-third of 150 ft). 2021 IBC Section 1007.1.1. Exception 2: NFPA 13 (903.3.1.1) or NFPA 13R (903.3.1.2) reduces the separation to one-third of the diagonal. Measured separation is short.
Table 1006.3.4(2) does not permit one exit. Limits are occupant load 49 and travel 100 ft.
Section 1007.1.2: where three or more exits are required, at least two must meet Section 1007.1.1. The others are arranged a reasonable distance apart.
Occupant load 600 on a story, NFPA 13, diagonal 150 feet, measured separation 48 feet.
Table 1006.3.3 requires 3 exits. Section 1007.1.1 Exception 2 requires 50 feet of separation, one-third of 150 feet. A measured separation of 48 feet does not comply. Two of the three exits have to meet that separation (Section 1007.1.2).
For a story, start with Table 1006.3.3, then check whether Section 1006.3.4 allows a single exit. For a room or space, Table 1006.2.1 sets when one exit access doorway is enough, and Section 1006.2.1.1 raises that to three or four at the same occupant-load steps. Separation is one-half the diagonal, or one-third when NFPA 13 or NFPA 13R is provided throughout. The number and arrangement of exits guide covers how reviewers measure remoteness on the plan.
Table 1006.3.3 requires 2 exits for an occupant load of 1 to 500, 3 for 501 to 1,000, and 4 for more than 1,000. Section 1006.3.4 can allow one exit when the story matches Table 1006.3.4(1) or Table 1006.3.4(2).
Section 1007.1.1 requires at least one-half of the maximum overall diagonal of the area served, measured in a straight line. Exception 2 reduces that to one-third where the building is sprinklered throughout with NFPA 13 or NFPA 13R. Where three or more exits are required, Section 1007.1.2 says at least two of them meet that separation.
The minimum number by occupant load per story is Table 1006.3.3. Section 1006.3.4, with Tables 1006.3.4(1) and 1006.3.4(2), is the single-exit allowance. This calculator applies both.
This calculator uses the 2021 International Building Code model text for general reference. Local amendments vary. It is not a substitute for the adopted code enforced by your authority having jurisdiction. See the jurisdiction pages for the edition a city has adopted, and scan the plan set before you rely on a result. A cell marked provisional was not confirmed from the model-code text and should not be used until you check the printed table.