Business occupant load: 100 gross in the 2015 IBC, 150 gross since 2018
One table value changed. Here is how it moves exits, door swing, corridors, and restroom counts for projects still on 2015-based codes.
An architect lays out a 6,000-square-foot office tenant space and writes the occupant load on the code sheet: 6,000 / 150 = 40. The reviewer marks it up: "Adopted building code is based on the 2015 IBC. Use 100 gross. Occupant load is 60." With 60 occupants, the space needs a second exit, the doors have to swing out, the corridor gets wider, and the restrooms need two more water closets.
The change behind that comment is one number in one table. The 2015 IBC assigns business areas 100 square feet gross per occupant. The 2018 IBC raised it to 150 gross, and the 2021 and 2024 editions kept 150. If your project is in a jurisdiction whose building code is still based on the 2015 IBC, every Group B occupant load you compute is 50 percent higher than it would be under a current code.
The two numbers
- 2015 IBC Table 1004.1.2: "Business areas, 100 gross."
- 2018 IBC Table 1004.5, 2021 IBC Table 1004.5, and the 2024 IBC: "Business areas, 150 gross," with a separate row for concentrated business use areas that points to Section 1004.8.
The same floor area gives two different counts. A 6,000 sq ft office is 60 occupants under the 2015 IBC and 40 under the 2018 or later IBC. The full factor table, by edition, is in occupant load factors by occupancy; this post is about what the higher 2015 count does downstream. Concentrated business uses such as call centers and training rooms have their own rule in the newer editions; see concentrated business use areas.
What the occupant load drives
Most of the Group B egress and plumbing thresholds did not move between 2015 and 2021. What moves is which side of each threshold your space lands on.
- One exit from a space (Table 1006.2.1). A Group B space may have one exit or exit access doorway with a maximum occupant load of 49. The common path of egress travel is 100 feet without sprinklers when the occupant load is 30 or less, 75 feet without sprinklers when it is more than 30, and 100 feet with sprinklers. The row is the same in the 2015, 2018, and 2021 IBC.
- One exit from a story. For Group B, the first story above or below grade plane may have one exit with up to 49 occupants, and the second story with up to 29, with a 75-foot limit (100 feet in a building sprinklered under 903.3.1.1). That is 2015 Table 1006.3.2(2) and 2021 Table 1006.3.4(2). The 2015 table measures the 75 feet as common path of egress travel; the 2021 table measures it as exit access travel distance.
- Door swing (Section 1010.1.2.1). Side-hinged doors must swing in the direction of egress travel when the room or area has an occupant load of 50 or more.
- Corridor width. 44 inches, or 36 inches with an occupant load of less than 50 (2015 Table 1020.2, 2021 Table 1020.3).
- Corridor rating. For Group B, a corridor serving more than 30 occupants is 1-hour without sprinklers and 0 with sprinklers (2015 Table 1020.1, 2021 Table 1020.2).
- Plumbing fixtures. The Group B row of IPC Table 403.1 is the same in the 2015, 2018, and 2024 IPC: water closets 1 per 25 for the first 50 and 1 per 50 after that; lavatories 1 per 40 for the first 80 and 1 per 80 after that; drinking fountains 1 per 100; one service sink, which is not required at 15 or fewer occupants. Section 403.1.1 splits the occupant load in half by sex and rounds each result up.
Example 1: 6,000 sq ft, one story, not sprinklered
- Occupant load: 60 under the 2015 IBC; 40 under the 2018 or later IBC.
- Exits from the space: 2015, two, because 60 is over 49. 2018+, one is permitted if the common path is 75 feet or less.
- Door swing: 2015, doors swing in the direction of egress (50 or more). 2018+, not required by 1010.1.2.1.
- Minimum corridor width: 2015, 44 inches. 2018+, 36 inches.
- Corridor rating: 1 hour under both, because both are over 30.
- Water closets: 2015, 30 per sex at 1 per 25 is 2 per sex, 4 total. 2018+, 20 per sex is 1 per sex, 2 total.
- Lavatories: 1 per sex, 2 total, under both.
- Drinking fountain and service sink: 1 and 1 under both.
The 2015 number pushes this space over three thresholds at once: the 49-occupant single-exit limit, the 50-occupant door swing, and the 50-occupant corridor width. It also doubles the water closet count.
Example 2: 4,000 sq ft on the second floor, not sprinklered
- Occupant load: 40 under the 2015 IBC; 26.7, rounded up to 27, under the 2018 or later IBC.
- Exits from the story: 2015, two, because the second-story limit is 29. 2018+, one is permitted within 75 feet.
- Common path within the space: 2015, 75 feet (over 30). 2018+, 100 feet (30 or less).
- Corridor rating: 2015, 1 hour (over 30). 2018+, no rating required by the table (30 or less).
- Water closets: 1 per sex under both.
Here the fixture count does not change, but the story exit count and the corridor rating do. A second-floor office that works with one stair under a current code needs two under a 2015-based code.
Separate restrooms
The 2018 IPC added an exception that drops separate men's and women's facilities for business occupancies with a maximum occupant load of 25 or fewer. The 2015 IPC does not have it; only the 15-or-fewer exception applies. So in a jurisdiction on 2015-based codes, a small office loses both ways: the higher occupant load and the missing exception. See IPC 403.2 separate facilities by edition and, for a 2021 plan-check walkthrough, when one restroom is enough.
Which jurisdictions are still on 2015-based codes
From our code adoption tracker, jurisdictions whose current building code is based on the 2015 IBC include:
- Washington, DC: the 2017 DC Construction Codes, which amend the 2015 IBC and 2015 IPC.
- Louisville, KY: the 2018 Kentucky Building Code, based on the 2015 IBC. Kentucky uses its own state plumbing code, not the IPC, so take fixture counts from that code.
- North Carolina: the 2018 North Carolina Building Code, which the Office of State Fire Marshal describes as based on the 2015 IBC. That covers Charlotte, Raleigh, Durham, Greensboro, Winston-Salem, Cary, and Fayetteville.
State and local amendments can change the occupant load table, the egress tables, and the plumbing fixture table. Check the amended text your jurisdiction adopted before you rely on any number in this post.
On the drawings
- State the code edition, and the occupant load factor you used, on the code sheet.
- Show the occupant load for each space and each story, not just the building total.
- Tie the exit count, door swing, corridor width, and corridor rating to those numbers.
- Tie the fixture count to the same occupant load.
The occupant load calculator lets you pick the 2015 factor or the current one, and the plumbing fixture calculator and how to calculate plumbing fixtures cover the restroom math.
Run a free scan on a tenant improvement set. An occupant load computed at the wrong factor for the adopted code is a comment the scan can surface before a reviewer does.
This is advisory. It is not a determination by the authority having jurisdiction. Confirm the adopted edition and local amendments before you change a drawing.