Occupant load = floor area ÷ occupant load factor. The factor is a density assumption: how many square feet the code presumes each person occupies in that function. A low factor means a dense space (lots of people); a high factor means a sparse one. (For how the resulting load drives exits and egress width, see our occupant load guide and means of egress guide.)
The most important rule in applying Table 1004.5: use the function of the space, not merely the building's occupancy classification. A business-classified building can contain a conference room used for assembly, a storage room, and a break-room kitchen — each takes its own factor based on what it's used for, not the building's overall Group B label. Applying one blanket factor across mixed functions is a common source of error.
The other make-or-break distinction:
Table 1004.5 specifies which basis applies to each function. Using gross where net is required (or vice versa) changes the result — a classroom computed on gross area yields a higher occupant load than the net basis the code intends.
| Function | Factor (sq ft / occupant) | Basis |
|---|---|---|
| Assembly, standing space | 5 | net |
| Assembly, concentrated (chairs only) | 7 | net |
| Assembly, unconcentrated (tables and chairs) | 15 | net |
| Classroom (educational) | 20 | net |
| Mercantile, basement and grade floor | 30 | gross |
| Exercise area / locker room | 50 | gross |
| Mercantile, upper floors | 60 | gross |
| Business areas | 150 | gross |
| Kitchens, commercial | 200 | gross |
| Parking garages | 200 | gross |
| Accessory storage, mechanical | 300 | gross |
These are common rows, not the full table — confirm the exact value for your function in Table 1004.5 of the edition your jurisdiction has adopted. (Concentrated business uses such as call centers can carry a denser factor under provisions added in the 2018 and later editions.)
A 3,000 sq ft restaurant dining area with tables and chairs: 3,000 ÷ 15 = 200 occupants (assembly, unconcentrated, net). At 200 occupants, the space needs two exits, doors swinging in the direction of egress, and egress width sized to that load. Re-run that same area at a business factor of 150 and you get 20 occupants — a tenfold error that would understate every egress requirement. The factor selection is the design.
This guide describes the model IBC for general understanding and is not a substitute for the adopted code and amendments enforced by your local authority having jurisdiction. Verify all figures against your jurisdiction's codes of record.