Last reviewed November 17, 2026. Citations are to the 2021 model codes unless a section says otherwise. Confirm the adopted edition on the jurisdictions page before you rely on a number.
“Where plumbing fixtures are required, separate facilities shall be provided for each sex.” That sentence is the same in the 2015, 2018, and 2021 IPC; the 2024 IPC says “separate toilet facilities.” The IBC copies the section into Section 2902.2, so the exceptions below apply whichever code your reviewer cites. Your jurisdiction may use a state plumbing code or the UPC instead of the IPC, and the wording there can differ.
| Exception (IPC 403.2) | 2015 | 2018 | 2021 | 2024 |
|---|---|---|---|---|
| 1. Dwelling units and sleeping units | Yes | Yes | Yes | Yes |
| 2. Total occupant load of 15 or fewer (employees and customers) | Yes | Yes | Yes | Yes |
| 3. Mercantile, maximum occupant load 100 or fewer | Yes | Yes | Yes | Yes |
| 4. Business, maximum occupant load 25 or fewer | No | Yes | Yes | Yes |
| 5. Single-user toilet rooms need not be designated by sex | No | No | Yes | Yes |
| 6. All-gender multiple-user rooms with privacy for water closets and urinals | No | No | Yes | Yes |
| 403.2.1: two family or assisted-use rooms serve as the separate facilities when each sex needs only one water closet | Yes | Yes | Yes | Not in the text |
The 2015 IPC has only Exceptions 1 to 3. The IBC 2902.2 list matches the IPC list in the 2018, 2021, and 2024 editions.
The occupant load comes from the building code. A 3,600 sq ft office is 24 occupants at the 150 gross business factor in the 2018 and later IBC, and 36 occupants at the 100 gross factor in the 2015 IBC. See Business occupant load: 100 vs. 150 gross and the occupant load calculator.
12-person office suite. The total occupant load is 15 or fewer, so Exception 2 applies in every edition and one toilet room is enough. Under note e to Table 403.1, a business occupancy of 15 or fewer also does not need a service sink.
3,600 sq ft office, 2018 or later code. 3,600 / 150 = 24 occupants. That is 25 or fewer, so Exception 4 applies and separate facilities are not required.
Same office, 2015 code. 3,600 / 100 = 36 occupants. The 2015 IPC has no business exception, so separate facilities are required. Half of 36 is 18 per sex, and the business ratio of 1 water closet per 25 gives one water closet per sex, so Section 403.2.1 lets two family or assisted-use rooms serve as the separate facilities.
60-person office, 2021 IPC, single-user rooms. With separate facilities, 30 per sex at 1 per 25 is two water closets per sex, four in total. Under Section 403.1.2 the total may be met with single-user rooms, so four single-user rooms can meet the count. Exception 5 means the single-user rooms are not designated by sex.
Run the numbers with the plumbing fixture calculator or follow the steps in how to calculate plumbing fixtures. Related guides: single-user and all-gender restrooms, commercial restroom requirements, and service sinks. For a plan-check walkthrough of the 2021 exceptions, see When one restroom is enough. Many states and cities amend these sections, so check your jurisdiction page and the code adoption tracker.
IPC 403.2 and IBC 2902.2 do not require separate facilities in dwelling and sleeping units, in structures or tenant spaces with a total occupant load of 15 or fewer (employees and customers), or in mercantile occupancies with a maximum occupant load of 100 or fewer. The 2018 and later editions add business occupancies of 25 or fewer. The 2021 and 2024 editions add single-user rooms that are not designated by sex and all-gender multiple-user rooms with private water closet compartments.
Under the 2018, 2021, or 2024 IPC, a business occupancy with a maximum occupant load of 25 or fewer does not need separate facilities. At the 150 gross business factor that is roughly 3,750 sq ft or less. The 2015 IPC has no business exception, so only the 15-or-fewer exception helps there.
Yes. IPC 403.1.2 says fixtures in single-user toilet and bathing rooms, including family or assisted-use rooms, contribute toward the total. The 2021 and 2024 editions let the total be met by any combination of single-user and separate facilities, and the 2024 edition deducts single-user fixtures proportionately from the gender ratios of Table 403.1.
In the 2021 and 2024 IPC, Section 403.1.1 Exception 2 says the minimum fixture count for multiple-user facilities designed to serve all genders is calculated at 100 percent of the total occupant load, and each fixture type must comply with ICC A117.1. Water closets need private compartments under Section 405.3.4.
This guide describes the model code for general understanding and is not a substitute for the adopted code and amendments enforced by your local authority having jurisdiction. Verify all figures against your jurisdiction's codes of record.