energy · high · OEESC 402, 403, 405
Building envelope (insulation R-values, U-factors for fenestration) does not comply with minimum energy efficiency requirements of OEESC Chapter 4.
Revise building envelope design to meet prescriptive or performance path requirements of OEESC, providing necessary insulation and fenestration U-factors.
egress · high · IBC 1005.1 (as adopted by Oregon OSSC)
Corridor/exit access width is insufficient for the calculated occupant load. Minimum 44 inches required where occupant load ≥ 50.
Increase corridor clear width to at least 44 inches, or reduce occupant load served by that path.
fire · high · OSSC 907.2
A fire alarm system is required by OSSC 907.2 but has not been shown or designed.
Provide a design for a fire alarm system per OSSC 907.6 and NFPA 72, including notification devices, initiating devices, and control panel.
structural · high · IBC 602 / OSSC — Construction Type
Proposed occupancy and/or building area/height exceeds the allowable limits for the stated construction type per IBC Tables 504 and 506.
Either redesign to a higher construction type, reduce building area/height, provide an automatic sprinkler system where it increases allowable area/height, or provide code analysis demonstrating compliance with area increase provisions.
completeness · medium · IBC 107 / Portland BDS Submittal Requirements
Submittal is incomplete: missing one or more of the following — site plan, floor plan with dimensions and occupant load calculations, construction type designation, code analysis sheet, egress plan, or energy compliance documentation.
Resubmit with a complete code analysis (occupancy, construction type, sprinkler status, occupant loads, egress widths/travel distances), fully dimensioned floor plans, and all required specialty reports.
accessibility · high · Oregon Accessibility Specialty Code (OASC) / ADA Standards — Chapter 11 IBC basis
Accessible route from public way/parking to primary building entrance and throughout tenant space is not provided or does not meet OASC requirements (slope, width, surfaces, protruding objects).
Provide a continuous accessible route meeting OASC; show accessible parking, ramps (max 1:12 slope), door clearances, and signage on plans.
energy · high · Oregon Reach Code / Oregon Energy Efficiency Specialty Code (OEESC) — ASHRAE 90.1 basis
Energy compliance documentation (COMcheck or equivalent) not provided, or proposed assembly U-values / LPD / mechanical efficiencies do not meet OEESC requirements.
Submit COMcheck compliance report (or ASHRAE 90.1 path documentation) showing envelope, lighting, and mechanical compliance. Portland may have adopted a reach code with stricter requirements — verify current Portland amendments.
fire · high · IBC 709 / 710 (OSSC) — Fire Partitions & Fire Barriers
Required fire-rated assembly (fire barrier or fire partition) is not detailed or rated construction is not specified on plans.
Provide UL-listed or IBC-prescriptive rated wall/floor/ceiling assembly details; specify fire-rated glazing, doors, and dampers as needed to maintain the rating.
accessibility · high · OASC (Oregon Accessibility Specialty Code) — Restroom Requirements
Accessible restroom does not comply with OASC: turning radius, grab bar placement, lavatory knee clearance, mirror height, or door hardware do not meet requirements.
Redesign restroom to provide 60-inch turning space, compliant grab bars at water closet, accessible lavatory with knee clearance, and lever/loop hardware. Provide detailed dimensioned restroom plan.
occupancy · high · Oregon Structural Specialty Code (OSSC) / IBC 508 & 302
Occupancy classification and/or mixed-occupancy separation requirements have not been adequately addressed on the drawings.
Clearly identify all occupancy groups on plans; provide required fire barriers or fire partitions for separated mixed occupancies per IBC Table 508.4, or demonstrate non-separated mixed occupancy compliance.
egress · high · IBC 1017.2 (OSSC)
Exit access travel distance of [X] ft exceeds the maximum allowable for occupancy group [Y] per IBC Table 1017.2.
Relocate exits or add additional exits to bring travel distances within code limits. Sprinkler protection may allow increased travel distance per code.
occupancy · medium · Oregon Mechanical Specialty Code (OMSC) / IMC 403
Mechanical ventilation rates do not meet minimum outside air requirements per OMSC/IMC Table 403.3 for the occupancy type and occupant load.
Revise mechanical schedules to provide minimum outside air per occupant and per square foot as required by OMSC Table 403.3. Provide mechanical plans stamped by Oregon-licensed mechanical engineer if required.
accessibility · high · OASC 1109.2, 1109.3 (adopting ICC A117.1)
Required accessible toilet facilities are not provided or do not comply with clear floor spaces, grab bar heights, or fixture clearances per OASC and ICC A117.1.
Redesign restroom layouts to meet accessible requirements, including clear floor space, grab bar locations, turning space, and fixture heights.
plumbing · medium · OPSC 403.1
The number of plumbing fixtures (water closets, lavatories, drinking fountains) does not meet the minimum required count for the proposed occupancy and occupant load.
Increase the number of plumbing fixtures as necessary to comply with OPSC Table 403.1 based on the calculated occupant load.
egress · high · OSSC 1010.1
Egress doors do not meet requirements for clear width, opening direction, or hardware (e.g., not readily openable without special knowledge).
Ensure all egress doors provide a minimum 32-inch clear width, swing in the direction of egress for occupant loads > 50, and have readily operable hardware.
fire · high · Oregon Fire Code (OFC) / IBC 903.2
Automatic fire sprinkler system is required but not shown on plans, or existing system coverage has not been extended into the new tenant improvement area.
Provide NFPA 13 (or 13R/13D as applicable) sprinkler system drawings; extend coverage throughout all new and modified spaces. Coordinate with Portland Fire & Rescue.
plumbing · high · Oregon Plumbing Specialty Code (OPSC) / IPC Table 403.1
Insufficient plumbing fixtures (water closets, lavatories, drinking fountains) provided for the calculated occupant load per OPSC Table 403.1.
Add fixtures to meet minimum counts for occupancy type and occupant load; provide accessible fixtures per Oregon Accessibility Specialty Code (OASC).
fire · high · OSSC 707, 708, 508.4, 506.2
Required fire-resistance rating for occupancy separation, area separation, or exit enclosures is not provided or details are insufficient.
Provide construction details and UL assemblies demonstrating compliance with required fire-resistance ratings for walls, floors, and opening protectives.
accessibility · high · OASC 1104.2 (adopting ICC A117.1)
An accessible route is not provided or does not meet minimum clear width, slope, or surface requirements from site arrival points to all accessible spaces.
Provide a continuous accessible route complying with OASC Chapter 11 and ICC A117.1 (e.g., 36-inch clear width, 1:12 max slope for ramps).
egress · high · OSSC 1004.1
Occupant load calculation is missing or incorrect for areas served by the egress system.
Provide a revised occupant load calculation per OSSC 1004.1 and update egress component capacities accordingly.
egress · high · OSSC 1013, 1014
Emergency lighting or exit signs are not provided, or are not in compliance with required locations, illumination levels, or visibility.
Install emergency lighting units to provide minimum illumination levels in egress paths and clearly visible, illuminated exit signs where required.
structural · high · OSSC 1603.1.5, 1604, 1607, 1608, 1609
Structural calculations for gravity and/or lateral loads (wind, seismic) are missing or insufficient to demonstrate compliance with OSSC Chapter 16 and material chapters.
Provide complete structural calculations, including foundation design, gravity loads, and lateral load resistance, signed and sealed by a registered design professional.
completeness · high · OSSC 107.1, 107.2
Construction documents are incomplete and lack necessary information (e.g., scope of work, code data, floor plans, sections, details, legend, stamp) required for review.
Submit permit application per OSSC 107 with complete construction documents