Accessible lavatory height and knee clearance: ADA 606
The 34-inch maximum to the higher of rim or counter, the knee and toe envelope under the bowl, the seven 606.2 exceptions, and why a vanity cabinet fails in a commercial restroom.
A vanity is drawn at 34 inches with a single bowl and a cabinet below. The accessibility reviewer writes: "Accessible lavatory has no knee and toe clearance. Provide clearance complying with 306 and insulate exposed supply and drain pipes. 606.2, 606.5." The counter height was right. What was under it was not.
Which lavatory has to comply
The 2010 ADA Standards for Accessible Design, published by the U.S. Department of Justice, scope lavatories and sinks separately:
- 213.3.4 Lavatories. "Where lavatories are provided, at least one shall comply with 606 and shall not be located in a toilet compartment."
- 212.3 Sinks. "Where sinks are provided, at least 5 percent, but no fewer than one, of each type provided in each accessible room or space shall comply with 606." Mop or service sinks are excepted.
So in a multi-user toilet room, the lavatory inside the accessible stall does not count. At least one lavatory outside the compartments has to meet 606.
Height: 34 inches to the higher of rim or counter
Section 606.3: "Lavatories and sinks shall be installed with the front of the higher of the rim or counter surface 34 inches (865 mm) maximum above the finish floor or ground."
The words "higher of" matter. A vessel bowl that sits on a 32-inch counter with a rim at 37 inches fails, even though the counter is low. Dimension the height to whichever is higher at the front edge.
There are two exceptions. A lavatory in a single-occupant toilet or bathing room accessed only through a private office, and not for common use or public use, does not have to meet 606.3. In residential dwelling unit kitchens, sinks adjustable between 29 and 36 inches are permitted where rough-in plumbing allows connection at the 29-inch height.
Forward approach with knee and toe clearance
Section 606.2 requires "a clear floor space complying with 305, positioned for a forward approach, and knee and toe clearance complying with 306." The clear floor space is 30 by 48 inches minimum (305.3). The knee and toe envelope under the bowl comes from Section 306:
- Knee clearance (306.3) is the space between 9 and 27 inches above the floor. It must be 30 inches wide minimum, 11 inches deep minimum at 9 inches above the floor, and 8 inches deep minimum at 27 inches. Between those heights it may reduce 1 inch in depth for each 6 inches in height. No more than 25 inches of depth counts.
- Toe clearance (306.2) is the space from the floor to 9 inches above it. Where it is required as part of a clear floor space it must extend 17 inches minimum under the element, 30 inches wide minimum, and 25 inches maximum. Space more than 6 inches beyond the available knee clearance at 9 inches does not count as toe clearance.
A base cabinet, a pedestal that intrudes into that envelope, or a trap and supply stops that hang low and forward will usually generate the comment. The clear floor space and knee and toe clearance post walks through the 305 and 306 geometry in more detail.
The 606.2 exceptions
Section 606.2 lists seven exceptions. The ones that come up most in plan review:
- A parallel approach is permitted to a kitchen sink in a space without a cooktop or conventional range, and to wet bars.
- A lavatory in a single-occupant toilet or bathing room accessed only through a private office, not for common use or public use, does not need knee and toe clearance.
- In residential dwelling units, cabinetry is permitted under lavatories and kitchen sinks only if the cabinetry can be removed without removing or replacing the fixture, the finish floor extends under the cabinetry, and the walls behind and around it are finished.
- At lavatories and sinks used primarily by children 6 through 12, a 24-inch minimum knee clearance is permitted where the rim or counter is 31 inches maximum.
- A parallel approach is permitted to lavatories and sinks used primarily by children 5 and younger.
- The dip of the overflow is not considered in determining knee and toe clearances.
- No more than one bowl of a multi-bowl sink must provide knee and toe clearance.
The residential cabinetry exception is not available in a commercial toilet room. A vanity cabinet under the accessible lavatory in an office or restaurant restroom is the usual failure.
Faucets and pipes
Section 606.4: "Controls for faucets shall comply with 309. Hand-operated metering faucets shall remain open for 10 seconds minimum." Section 309.4 requires operable parts to be operable with one hand, without tight grasping, pinching, or twisting of the wrist, at 5 pounds of force maximum.
Section 606.5: "Water supply and drain pipes under lavatories and sinks shall be insulated or otherwise configured to protect against contact. There shall be no sharp or abrasive surfaces under lavatories and sinks." A note or detail calling out pipe protection answers this on the drawings.
The advisory to 606.1 adds that if soap and towel dispensers are provided, they must be within the reach ranges in Section 308. The ADA reach range calculator checks those heights.
What the 2010 ADA Standards do not settle here
Buildings permitted under the International Building Code also have to meet the ICC A117.1 edition the adopted IBC references, and its lavatory provisions can differ from 2010 ADA 606. This post does not quote A117.1. Confirm the standard and edition the authority having jurisdiction enforces, and see IBC, ADA, and ICC A117.1: which accessibility rule applies and the accessible restroom basics guide.
Check the layout
The ADA lavatory and sink calculator checks rim or counter height, the knee and toe envelope, clear floor space, faucet force and metering time, and the 212.3 and 213.3.4 scoping against 2010 ADA 606. For the water closet next to it, use the accessible water closet calculator.
On the drawings
- Dimension the front of the higher of the rim or counter, 34 inches maximum.
- Show a section through the accessible lavatory with knee clearance at 9 and 27 inches and toe clearance to 9 inches.
- Remove the base cabinet under the accessible lavatory unless it is in a dwelling unit and meets all three conditions of the exception.
- Note pipe insulation or protection under the bowl.
- Specify faucets that meet 309.4, and 10-second minimum run time if metering.
- In multi-user rooms, locate the compliant lavatory outside the toilet compartments.
Run a free scan on your plans. A missing knee clearance at the accessible lavatory is the kind of comment the scan can surface before a reviewer does.
This is advisory. It is not a determination by the authority having jurisdiction. Confirm the adopted accessibility standard, its edition, and any local amendments before you change a drawing.