Allowable height in feet, allowable stories, and allowable area per story from 2021 IBC Tables 504.3, 504.4, and 506.2, with the Table 506.3.3 frontage increase.
Edition: 2021 IBC model text. Sprinkler rows are NS (none), S / S1 / SM (NFPA 13), and S13R (NFPA 13R, Group R).
At (S1) = 72000. NS = 18000. If = 0.5 (2021 IBC Table 506.3.3).
Mixed occupancy (Section 508), unlimited area (Section 507), and Section 510 special provisions are not applied.
Group B, Type V-A, one story, NFPA 13, 50 percent frontage, open space over 30 feet.
Table 504.3 height is 70 ft. Table 504.4 allows 4 stories. Equation 5-1 uses At = 72,000 (S1) and NS = 18,000 with If = 0.5. Allowable area per story is 81,000 sq ft. This is the ICC 2021 heights-and-areas example.
Pick the occupancy and construction type, then the sprinkler system. Height and stories come straight from the matching table row. Area per story is At + (NS × If). A one-story NFPA 13 building uses S1. Two or more stories use SM. NFPA 13R uses the S13R row where the table has one, and otherwise does not take the NFPA 13 increase. Frontage qualifies only when at least 25 percent of the perimeter fronts a public way or open space at least 20 feet wide. The increase is the printed Table 506.3.3 factor for that band.
See the allowable height and area guide for how reviewers check the code sheet against the declared type, occupancy, and sprinklers.
The 2021 International Building Code. Height in feet is Table 504.3, stories are Table 504.4, area factors are Table 506.2, and the frontage increase is Table 506.3.3. Local amendments vary. Check the jurisdiction page for the adopted edition, and scan the plan set against that edition.
No. Read the NS, S, or S13R row. The sprinkler increase is already built into those rows, and some groups do not receive one. NFPA 13R heights and stories are tabulated for Group R. An NFPA 13 building uses the S row for height and stories, the S1 area factor when it is one story above grade plane, and the SM factor when it is two or more stories.
Section 506.2.1 Equation 5-1: allowable area per story equals At plus NS times If. At is the tabular factor for the sprinkler condition. NS is the nonsprinklered factor even when the building is sprinklered. If is the Table 506.3.3 factor for the frontage band. The calculator uses the printed band value. Footnote a permits interpolation, and the ICC examples use the band.
This calculator uses the 2021 International Building Code model text for general reference. Local amendments vary. It is not a substitute for the adopted code enforced by your authority having jurisdiction. See the jurisdiction pages for the edition a city has adopted, and scan the plan set before you rely on a result. A cell marked provisional was not confirmed from the model-code text and should not be used until you check the printed table.