Fire Separation Distance and Exterior Wall Openings

Exterior wall fire-resistance rating from 2021 IBC Table 705.5 and the maximum unprotected and protected opening area from Table 705.8.

Edition: 2021 IBC model text. The opening percentage is the share of the exterior wall area of that story.

Required exterior wall rating
0 hours

2021 IBC Table 705.5, 10 feet to less than 30 feet.

Opening limits, Table 705.8

Applied unprotected limit (Unprotected, nonsprinklered (UP, NS)): 15%. Protected openings: 45%.

UP, NS 15%. UP, S 45%. P 45%. 10 to less than 15 feet.

Load-bearing exterior walls also comply with Table 601.

The rating is read for the fire separation distance of that wall and the story where the wall is located.

Group R-3 with a fire separation distance of 5 feet or greater does not have a limited opening area. From 3 feet to less than 5 feet, Group R-3 is limited to 25 percent.

An open parking structure with a fire separation distance of 10 feet or greater does not have a limited opening area.

A building containing only a Group U private garage or carport with a fire separation distance of 5 feet or greater does not have a limited opening area.

Worked example

Group B, Type V-B, fire separation distance 12 feet, no sprinklers.

Table 705.5, for 10 feet to less than 30 feet and Type V-B, rates the Group B wall at 0 hours. Table 705.8, for 10 feet to less than 15 feet, limits unprotected nonsprinklered openings to 15%. Protected openings at that distance are 45%.

How this is calculated

Enter the fire separation distance of the wall you are checking, the construction type, and the occupancy that sets the Table 705.5 column. Table 705.8 then gives three opening limits: unprotected without NFPA 13, unprotected with NFPA 13, and protected. NFPA 13R stays in the unprotected nonsprinklered column. The exterior wall guide is the place to line the site plan up with the elevations.

FAQ

What is fire separation distance?

It is the distance from the exterior wall to the closest interior lot line, to the centerline of a street, alley, or public way, or to an imaginary line between two buildings on the same lot. Table 705.5 and Table 705.8 are read for that distance on each story.

Which table sets the exterior wall rating?

Table 705.5 sets the hourly rating from the fire separation distance, the construction type, and the occupancy group. Load-bearing exterior walls also have to meet Table 601. Group H has further rules in Section 415.6.

Which opening percentage applies?

Table 705.8. Unprotected openings in a building sprinklered throughout with NFPA 13 use the UP, S column. Other unprotected openings use UP, NS. Protected openings use the P column. NFPA 13R does not qualify for UP, S, and UP, S does not apply to Groups H-1, H-2, and H-3.

Check your full plan set →

This calculator uses the 2021 International Building Code model text for general reference. Local amendments vary. It is not a substitute for the adopted code enforced by your authority having jurisdiction. See the jurisdiction pages for the edition a city has adopted, and scan the plan set before you rely on a result. A cell marked provisional was not confirmed from the model-code text and should not be used until you check the printed table.