Travel Distance and Common Path Calculator

Exit access travel distance from 2021 IBC Table 1017.2 and common path of egress travel from Table 1006.2.1, by occupancy and sprinkler status.

Edition: 2021 IBC model text. Sprinkler columns follow the table footnotes: some rows accept NFPA 13 or 13R, and some require NFPA 13.

Selects the Table 1006.2.1 common-path column.
Optional. Compared with Table 1017.2.
Exit access travel distance
300 ft

2021 IBC Table 1017.2 Measured distance complies.

Common path of egress travel
100 ft

2021 IBC Table 1006.2.1. with sprinkler system. One exit from the space by occupant load: within the table maximum.

Footnote c: the sprinklered distance requires NFPA 13 throughout (Section 903.3.1.1). NFPA 13R does not qualify.

Worked example

Group B, occupant load 40, NFPA 13, measured travel 240 feet.

Table 1017.2 allows 300 ft with NFPA 13, so 240 feet complies. Table 1006.2.1 common path for this sprinklered Group B space is 100 ft. The same Group B building with only NFPA 13R stays at 200 feet of travel distance, because footnote c requires NFPA 13.

How this is calculated

Travel distance is the Table 1017.2 limit for the occupancy. The sprinklered number is used only when the selected system matches the footnote. Section 1017.2.2 can raise Group F-1 and S-1 to 400 feet when the space is one story, the clear height is at least 24 feet, and the building has NFPA 13. Common path uses Table 1006.2.1, including the split at an occupant load of 30 when the space is not sprinklered. The travel distance guide describes how the path is measured on the plan.

FAQ

Where is exit access travel distance measured?

Section 1017.3 measures it from the most remote point, along the natural and unobstructed path, to an exit. It is not a straight line across the room. Common path, from Table 1006.2.1, stops where two separate paths become available.

Does NFPA 13R increase the travel distance for every occupancy?

No. Table 1017.2 footnote b lets NFPA 13 or NFPA 13R qualify for Groups A, E, F-1, I-1, M, R, and S-1. Footnote c, which includes Group B, F-2, S-2, U, H-5, I-2, I-3, and I-4, requires NFPA 13. An NFPA 13R Group B building stays at 200 feet.

Why does the unsprinklered common path change at 30 occupants?

Table 1006.2.1 prints two without-sprinkler columns: occupant load of 30 or less, and occupant load greater than 30. Group B is 100 feet and then 75 feet. The sprinklered column is a single value when the sprinkler system qualifies.

Check your full plan set →

This calculator uses the 2021 International Building Code model text for general reference. Local amendments vary. It is not a substitute for the adopted code enforced by your authority having jurisdiction. See the jurisdiction pages for the edition a city has adopted, and scan the plan set before you rely on a result. A cell marked provisional was not confirmed from the model-code text and should not be used until you check the printed table.