Last reviewed November 12, 2026. Citations are to the 2021 model codes unless a section says otherwise. Confirm the adopted edition on the jurisdictions page before you rely on a number.
One- and two-family dwellings and townhouses that fall under the IRC use Section R310. Apartments and other Group R buildings under the IBC use Section 1031. The dimensions travel well. The “where required” rules do not. That is the useful answer to the question of whether residential egress windows are the same nationwide: the net-clear size has been stable in recent model editions, and the duty to provide the opening depends on which code applies and on local amendments. Confirm both on the jurisdictions page.
These openings are not the means of egress. A house still needs its required exit doors and stairs. An EERO is the firefighter-in, occupant-out opening from a sleeping room or basement. Do not size it with the egress width calculator, and do not confuse it with IBC stair geometry.
IRC 2021 §§R310.2.1 through R310.2.3 and IBC 2021 §§1031.3.1 through 1031.3.3 match on the numbers reviewers check:
The arithmetic reviewers do in their head: 20 inches times 24 inches is 480 square inches, and 5.7 square feet is 820.8 square inches. A window that only meets the two minimum dimensions fails the area. At a 24-inch clear height you need about 34.2 inches of clear width. At a 20-inch clear width you need about 41 inches of clear height. Put the clear width, clear height, and net clear area on the window schedule for every sleeping room and basement opening you are claiming.
The grade-floor reduction to 5.0 square feet applies only to an opening the code defines as grade floor — in the IRC, an opening whose bottom of clear opening is not more than 44 inches above or below finished ground adjacent to the opening. Confirm that definition in the adopted IRC before you use 5.0. A second-floor bedroom does not get the reduction because the yard is “at grade” somewhere below it.
Public text for the residential side is widely republished by building departments from IRC R310. The City of Evanston’s emergency escape and rescue opening guide quotes the 2021 IRC size rules. The IBC size rules are in 2021 IBC Chapter 10, Section 1031. The IRC chapter is 2021 IRC Chapter 3.
IRC 2021 §R310.1 requires at least one operable emergency escape and rescue opening in basements, habitable attics, and every sleeping room. Where a basement contains sleeping rooms, each of those sleeping rooms needs one. The opening has to open directly onto a public way, or onto a yard or court at least 36 inches wide that opens to a public way.
Below-grade openings need an area well under §R310.4. Municipal handouts quoting that section describe a well with at least 9 square feet of horizontal area and a minimum dimension of 36 inches, and a permanently affixed ladder or steps when the well is more than 44 inches deep. Ladder geometry in those handouts follows §R310.4.2: at least 12 inches wide inside, projecting at least 3 inches, and spaced not more than 18 inches on center. Confirm the well section in the adopted IRC. Replacement windows have a separate allowance in §R310.2.5 for the manufacturer’s largest standard size that fits an existing frame or rough opening. That allowance does not apply to a new opening.
IBC 2021 §1031.2 is the “where required” section, and it is narrower than the IRC. A City of Bellevue multifamily checklist written to the 2021 IBC tells applicants to provide emergency escape and rescue openings in Group R-2 occupancies located on stories with only one exit or access to one exit, under §1006.3.4, and to show location, size, and sill height where §1031 requires them. Published explanations of §1031.2 also include Group R-3 and R-4, and then require the opening in basements and sleeping rooms below the fourth story above grade plane when those triggers apply.
The section has exceptions, including cases where a door opens directly to a public way, yard, or court, and a sprinkler exception for certain basement dwelling or sleeping units. The exception text is easy to over-read. Open §1031.2 in the adopted IBC and apply the exceptions from the printed list rather than from a summary. A fully sprinklered R-2 building with two exits from the story is often outside the trigger entirely, which is why many apartment sleeping rooms have no egress window and still comply.
This guide describes the model code for general understanding and is not a substitute for the adopted code and amendments enforced by your local authority having jurisdiction. Verify all figures against your jurisdiction's codes of record.