Last reviewed November 12, 2026. Citations are to the 2021 model codes unless a section says otherwise. Confirm the adopted edition on the jurisdictions page before you rely on a number.
Sprinklers and standpipes have their own sheets. Extinguishers are usually a symbol on the life-safety plan, and the comment is that the symbol does not prove a travel distance. The fire code official measures along the path a person walks, around racks and through doors, not as a circle drawn through walls. Section 906.2 requires extinguishers to be selected, installed, and maintained in accordance with NFPA 10. The IFC reprints the Class A distribution table so you can do the count without leaving the fire code, then sends the installation details to the standard.
Read Section 906 in the 2021 IFC Chapter 9. NFPA 10 is the referenced standard; the NFPA page for the document is nfpa.org/codes-and-standards. This is not a substitute for a sprinkler system. See when sprinklers are required and standpipes.
Section 906.3.1 sends ordinary combustible hazards to Table 906.3(1). The model table:
| Light (low) | Ordinary (moderate) | Extra (high) | |
|---|---|---|---|
| Minimum rated single extinguisher | 2-A | 2-A | 4-A |
| Maximum floor area per unit of A | 3,000 sq ft | 1,500 sq ft | 1,000 sq ft |
| Maximum floor area per extinguisher | 11,250 sq ft | 11,250 sq ft | 11,250 sq ft |
| Maximum travel distance | 75 feet | 75 feet | 75 feet |
Two footnotes change the arithmetic. For light hazard, two water-type extinguishers rated 1-A each may be treated as one 2-A extinguisher. For extra hazard, two 2-1/2-gallon water-type extinguishers may be treated as one 4-A extinguisher. A common 2-A:10-B:C multipurpose extinguisher satisfies the minimum rating for light and ordinary Class A hazards. It does not satisfy a Class K cooking hazard.
The area allowance and the travel distance both apply, and travel distance usually governs. A light-hazard floor could theoretically put a lot of square feet on one 2-A unit and still fail because someone in the far corner walks more than 75 feet. Show the path on the plan for the longest walk, not only the count.
Table 906.3(2) covers flammable or combustible liquids with a depth of 1/4 inch or less. Light hazard is a 5-B extinguisher within 30 feet or a 10-B within 50 feet. Ordinary hazard is 10-B within 30 feet or 20-B within 50 feet. Extra hazard is 40-B within 30 feet or 80-B within 50 feet. Deeper liquid hazards are sent on to NFPA 10. Do not use the 75-foot Class A distance for a fuel or solvent room.
Section 906.1 is the “where required” list. It includes most occupancies other than one- and two-family dwellings, and it names special hazards, including commercial cooking. Kitchens that produce grease-laden vapors are a Class K problem under NFPA 10, in addition to the hood suppression system in the UL 300 guide and the Type I and Type II hood guide. The travel distance for that cooking extinguisher is amended often. Read the adopted IFC §906 and NFPA 10 before you write a single footage on the kitchen plan. This guide intentionally does not state a Class K distance.
Mounting, which reviewers do check against an elevation or a note:
Locate them where they can be seen along the normal path of travel. A unit inside a closet, or blocked by the equipment it is there to protect, fails even when the distance math works. Where a cabinet or a column hides the unit, the fire code expects a sign.
This guide describes the model code for general understanding and is not a substitute for the adopted code and amendments enforced by your local authority having jurisdiction. Verify all figures against your jurisdiction's codes of record.