Exit separation: the half-diagonal rule in IBC 1007.1.1
Where two exits are required, 2021 and 2024 IBC Section 1007.1.1 sets one-half the diagonal, or one-third when sprinklered throughout. Measurement points, the rated corridor exception, and stairs.
A tenant suite is drawn with two exit access doorways a few feet apart on the same corridor wall. The reviewer writes: "Exit access doorways are not separated by one-half of the maximum overall diagonal dimension of the area served. 1007.1.1." The suite has the right number of doors. They are just in the wrong places.
The rule
The 2021 International Building Code, Chapter 10, Section 1007.1.1, reads:
"Where two exits, exit access doorways, exit access stairways or ramps, or any combination thereof, are required from any portion of the exit access, they shall be placed a distance apart equal to not less than one-half of the length of the maximum overall diagonal dimension of the building or area to be served measured in a straight line between them. Interlocking or scissor stairways shall be counted as one exit stairway."
Three things in that sentence generate most comments:
- It applies where two are required. Section 1006 decides whether a room, space, or story needs two exits or exit access doorways. If one is enough under Section 1006, the separation rule does not kick in. See When one exit is enough: IBC 1006.3.4 and Common path of egress travel: IBC Table 1006.2.1.
- The diagonal is of the building or area served. For a suite, it is the suite's maximum overall diagonal. For a story, it is the story's.
- The separation is a straight line between them. Not the walking path. The one written exception to that is below.
The 2024 IBC Chapter 10 keeps Section 1007.1.1, its two exceptions, and the 1007.1.1.1 measurement points with the same wording.
The two exceptions
Exception 1, rated corridor. "Where interior exit stairways or ramps are interconnected by a 1-hour fire-resistance-rated corridor conforming to the requirements of Section 1020, the required exit separation shall be measured along the shortest direct line of travel within the corridor." This changes how the distance is measured, for interior exit stairways and ramps only. It does not reduce the required distance. The rated corridors guide covers when a corridor has to be rated.
Exception 2, sprinklers. "Where a building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2, the separation distance shall be not less than one-third of the length of the maximum overall diagonal dimension of the area served." "Throughout" is the operative word. A sprinklered tenant space in a building that is not sprinklered throughout does not get the one-third.
Where to measure from
Section 1007.1.1.1 sets the measurement points:
- To exit or exit access doorways, measure to any point along the width of the doorway.
- To exit access stairways, measure to the closest riser.
- To exit access ramps, measure to the start of the ramp run.
So for two doors, the measurement may be taken to any point within each opening's width, not only center to center. For a stair, it is the closest riser, not the stair's far end.
A worked example
A suite is 100 feet by 60 feet. Its diagonal is the square root of 100² + 60², about 116.6 feet.
- Not sprinklered throughout: one-half, about 58.3 feet between the two exit access doorways.
- Sprinklered throughout under 903.3.1.1 or 903.3.1.2: one-third, about 38.9 feet.
Two doors 20 feet apart on the same wall fail both. Moving one door to the far end of that wall, or to an adjacent wall, is the usual fix. The exits and exit separation calculator runs the count from 2021 IBC Table 1006.3.3 and the one-half or one-third separation, and the travel distance calculator checks the other egress limit that often moves with the doors.
Three or more, and stairs
Section 1007.1.2: where access to three or more exits is required, "not less than two exit or exit access doorways shall be arranged in accordance with the provisions of Section 1007.1.1." The others must be "a reasonable distance apart so that if one becomes blocked, the others will be available."
Section 1007.1.3: where two exit access stairways or ramps provide the required means of egress to exits at another story, "the required separation distance shall be maintained for all portions of such exit access stairways or ramps." Where more than two are provided, at least two must meet that (1007.1.3.1). Two open stairs that start far apart but land side by side do not comply. The exit access stairways guide covers when an open stair is allowed at all.
And interlocking or scissor stairs count as one exit stairway, so a scissor stair cannot satisfy both required exits by itself.
On the drawings
- Draw the maximum overall diagonal of the building or area served and label its length.
- Draw the straight-line separation between the two exits or exit access doorways, measured to the points in 1007.1.1.1, and label it.
- State whether the building is sprinklered throughout under 903.3.1.1 or 903.3.1.2 if you use the one-third.
- If you rely on Exception 1, show the 1-hour corridor and the travel line within it.
- For exit access stairways, show the separation is kept along the full stair, not only at the top.
See the number and arrangement of exits guide for the full picture, and check which IBC edition your jurisdiction has adopted on the jurisdictions page.
Run a free scan on your plans. Exits placed too close together are the kind of comment the scan can surface before a reviewer does.
This is advisory. It is not a determination by the authority having jurisdiction. Confirm the adopted code, its edition, and any local amendments before you change a drawing.