Building Element Fire-Resistance Rating Calculator (IBC Table 601)

Required hourly ratings for the primary structural frame, bearing walls, nonbearing walls, floors, and roofs by construction type, with the Table 601 footnotes and the Table 705.5 exterior wall check.

Edition: 2021 IBC model text, Table 601 and footnotes a through g, Sections 602.1 through 602.5, and Table 705.5 for exterior walls. Local amendments and the 2024 IBC are not applied.

Used for footnote b and Table 705.5.
For exterior walls (footnote e, Table 705.5).
Type II-A, 2021 IBC Table 601
Building elementRequired ratingBasis
Primary structural frame b, c, f1 hrTable 601, Type II-A
Bearing walls, exterior e, f1 hrTable 601, Type II-A
Bearing walls, interior1 hrTable 601, Type II-A
Nonbearing walls and partitions, exteriorSee Table 705.5Table 601 refers to Table 705.5; enter the occupancy and fire separation distance
Nonbearing walls and partitions, interior d0 hrTable 601, Type II-A
Floor construction and associated secondary structural members1 hrTable 601, Type II-A
Roof construction and associated secondary structural members b, c1 hrTable 601, Type II-A

Exterior bearing walls must also meet Table 705.5 for their fire separation distance (footnote e). Enter the occupancy and distance to check it.

Footnote c: heavy timber complying with Section 2304.11 is allowed for roof construction, including primary frame members, where 1 hour or less is required.

Footnote f: the primary frame and exterior bearing walls are also not less than the rating referenced in Section 704.10.

Footnote d: interior nonbearing walls are 0 hours under Table 601 but take any rating required elsewhere in the code, such as corridors, shafts, fire barriers, and separations.

Table 601 footnotes (2021 IBC)

  1. Roof supports: Fire-resistance ratings of primary structural frame and bearing walls are permitted to be reduced by 1 hour where supporting a roof only.
  2. Except in Group F-1, H, M and S-1 occupancies, fire protection of structural members in roof construction shall not be required, including protection of primary structural frame members, roof framing and decking where every part of the roof construction is 20 feet or more above any floor immediately below. Fire-retardant-treated wood members shall be allowed to be used for such unprotected members.
  3. In all occupancies, heavy timber complying with Section 2304.11 shall be allowed for roof construction, including primary structural frame members, where a 1-hour or less fire-resistance rating is required.
  4. Not less than the fire-resistance rating required by other sections of this code.
  5. Not less than the fire-resistance rating based on fire separation distance (see Table 705.5).
  6. Not less than the fire-resistance rating as referenced in Section 704.10.
  7. Heavy timber bearing walls supporting more than two floors or more than a floor and a roof shall have a fire resistance rating of not less than 1 hour.

Worked example

Type II-A, a Type V-A office wall 4 feet from the lot line, a Type II-B warehouse wall at 4 feet, and a Type I-A roof more than 20 feet up.

Type II-A reads 1 hr for the primary frame, 1 hr for bearing walls, 1 hr for floors, and 1 hr for the roof. A Type V-A Group B exterior bearing wall 4 feet from the line is 1 hr in Table 601 and 1 hr in Table 705.5, so it is 1 hr. A Type II-B Group S-1 exterior bearing wall at 4 feet is 0 hr in Table 601, but footnote e sends it to Table 705.5, which requires 2 hr. A Type I-A Group B roof whose construction is 20 feet or more above the floor below drops from 1 1/2 hr to 0 hr under footnote b, while the floor stays 2 hr.

How this is calculated

  1. Confirm the construction type. Use the type declared on the code sheet, Type I-A through V-B, including the four Type IV columns (IV-A, IV-B, IV-C, IV-HT). Sections 602.2 through 602.5 define what each type is built from.
  2. Read the Table 601 row for each element. Read the hours for the primary structural frame, exterior and interior bearing walls, interior nonbearing walls, floor construction, and roof construction in that type's column of 2021 IBC Table 601.
  3. Apply the footnotes that change a number. Footnote a lowers the frame and bearing walls by 1 hour where they support a roof only. Footnote b removes roof protection where the roof construction is 20 feet or more above the floor below, except in Groups F-1, H, M, and S-1. Footnote g sets Type IV-HT interior bearing walls to 1 hour where they support more than two floors or a floor and a roof.
  4. Check exterior walls against Table 705.5. Footnote e makes an exterior bearing wall not less than the Table 705.5 rating for its fire separation distance, occupancy, and type. Nonbearing exterior walls take the Table 705.5 rating directly.
  5. Add ratings required by other sections. Interior nonbearing walls are 0 hours in Table 601, but corridors, shafts, fire barriers, fire partitions, and occupancy separations carry their own ratings (footnote d). The frame is also not less than Section 704.10 requires (footnote f).

The construction type has to support the building's height and area; check it with the allowable height and area calculator. Exterior wall openings are limited separately in Table 705.8; use the exterior wall and openings calculator. The construction type guide explains Types I through V.

FAQ

What does IBC Table 601 require for each construction type?

Table 601 of the 2021 IBC sets hourly ratings for the primary structural frame, bearing walls, nonbearing walls, floors, and roofs. Type I-A is 3 hours for the frame and bearing walls, 2 hours for floors, and 1 1/2 hours for the roof. Type I-B is 2, 2, 2, and 1. Types II-A, III-A, and V-A are 1-hour construction for the frame, floors, and roof. Types II-B, III-B, and V-B have no frame, floor, or roof rating. Local amendments vary, so check the jurisdiction page for the adopted edition.

Why is my exterior bearing wall rating higher than Table 601?

Footnote e makes an exterior bearing wall not less than the rating Table 705.5 requires for its fire separation distance. A Type II-B Group S-1 bearing wall 4 feet from the lot line is 0 hours in Table 601 but 2 hours in Table 705.5, so it needs 2 hours. Nonbearing exterior walls are rated by Table 705.5 alone.

When can a roof or roof framing go unprotected?

Footnote b drops the protection of roof construction, including primary frame members in the roof, roof framing, and decking, where every part of the roof construction is 20 feet or more above any floor immediately below. It does not apply to Groups F-1, H, M, and S-1. Footnote a separately lets the frame and bearing walls drop 1 hour where they support a roof only.

Check your full plan set →

This calculator uses the 2021 International Building Code model text for general reference. Local amendments vary. It is not a substitute for the adopted code enforced by your authority having jurisdiction. See the jurisdiction pages for the edition a city has adopted, and scan the plan set before you rely on a result. A cell marked provisional was not confirmed from the model-code text and should not be used until you check the printed table.